What it means
F07404 is the drive's DC link overvoltage monitoring: it reports that the DC link voltage rose to the upper threshold while that monitoring was enabled, or — in U/f control — that the Vdc_max monitoring built on p1284 responded. The manuals title the code either "Drive: Upper DC link voltage threshold reached" or "Drive: DC link voltage monitoring Vdc_max"; both describe the same condition. On the G120XA the code also fires when kinetic buffering ends and the line supply has not come back in time.
The fault trips the drive, and it must be acknowledged before the drive will start again.
Why it appears
- The DC link voltage monitoring is enabled (p1240, p1280 = 4 or 6) and the DC link voltage climbs to the upper threshold (r1242, r1282) while the drive is in the "Operation" state — printed for the G130, the G150 and for S120/S150 with the vector drive objects.
- On S120/S150 with the servo drive objects the same monitoring (p1240 = 4 or 6) reacts when the upper DC link voltage threshold p1244 is reached in the "Operation" state.
- In U/f control, the Vdc_max monitoring configured in p1284 responded — this is the only cause the manual prints for the G120.
- For S120/S150 vector entries, the DC link voltage control is available because the technology controller is activated, and the supply voltage (p0210, p0212) has been reduced.
- G120XA, kinetic buffering: while buffering was running, the speed dropped below the minimum speed (p1257, or p1297 for vector drives with U/f control) and the line supply stayed away.
- G120XA, kinetic buffering: the maximum buffer time (p1255, and p1295 for vector drives with U/f control) ran out before the line supply came back.
What to check
- Check the line supply voltage — every manual that describes this code starts its remedy here.
- Check the infeed. The G120 and G120XA remedies name the braking module; the S120/S150 servo remedy says to check the infeed unit or the Braking Module.
- Adapt the setting for the device line supply voltage, p0210. For S120/S150 with the vector drive objects the remedy additionally sets p0212.0 = 0.
- On S120/S150 with the servo drive objects, increase the upper DC link voltage threshold (p1244).
- Where the monitoring is not needed, switch it off: p1240 = 0, on the G130, G150 and S120/S150 vector entries together with p1280 = 0.
- In U/f control, adapt the Vdc_max monitoring (p1284) — the closing step for G120, G120XA, G130/G150 and S120/S150 vector.
Parameters the manual names
- p0210 — the drive unit's line supply voltage setting; every remedy adapts it to the voltage actually present.
- p0212 — power unit configuration; in the S120/S150 vector remedy, bit 0 is set to 0 (p0212.0 = 0) while adapting the supply voltage.
- p1240 — configuration of the Vdc monitoring: 4 or 6 have it active for this fault, 0 deactivates it.
- p1280 — the U/f counterpart of p1240; on G130/G150 and S120/S150 vector entries it is switched off together with p1240.
- p1244 — upper DC link voltage threshold in the S120/S150 servo entries; the remedy raises it.
- p1284 — time threshold of the Vdc_max monitoring in U/f control; its response is a cause in the G120, G120XA, G130/G150 and S120/S150 vector entries and it is adapted in their remedies.
- p1257 — speed threshold of the Vdc_min controller, named in the G120XA cause when the speed falls below it during kinetic buffering.
- p1297 — the U/f variant of that speed threshold, named for vector drives with U/f control.
- p1255 — time threshold of the Vdc_min controller, i.e. the maximum buffer time in the G120XA cause.
- p1295 — U/f variant of that buffer time for vector drives with U/f control.
- r1242 — the upper threshold level (Vdc_max switch-in level) whose being reached in the "Operation" state raises the code in the vector entries.
- r1282 — the U/f counterpart of r1242.
Acknowledging and restarting
Once the cause is removed, acknowledge the fault at the operator panel or in the commissioning tool; the drive starts again only after that acknowledgment.
What differs between the drive families
Straight from the manuals' own fields — F07404 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | OFF2 (NONE, OFF1, OFF3) OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) OFF3 (IASC/DCBRK, NONE, OFF1, OFF2, STOP2) | IMMEDIATELY IMMEDIATELY IMMEDIATELY | — | — | SINAMICS G120XA PN converter · p. 1128 |
| S120, S150 | OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY | DC link overvoltage (4) | None | SINAMICS S120, S150 List Manual · p. 2800 |
| G130, G150 | OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY | DC link overvoltage (4) | None | SINAMICS G130, G150 List Manual · p. 1545 |
| S120, S150 | OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY | DC link overvoltage (4) | None | SINAMICS S120, S150 List Manual · p. 2800 |
| G120 | OFF2 (NONE, OFF1, OFF3) | IMMEDIATELY | DC link overvoltage (4) | — | SINAMICS G120 · p. 877 |
The drives this code lives on
F07404 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07404 mean on a SINAMICS drive?
That the DC link voltage reached its upper threshold while monitoring was enabled (r1242/r1282, or p1244 on the servo side), that the Vdc_max monitoring (p1284) responded in U/f control, or — on the G120XA — that kinetic buffering ended without the line supply returning.
How do I fix F07404?
Work through the checks in order: line supply voltage, infeed or braking module, then adapt p0210 (with p0212.0 = 0 on S120/S150 vector), raise p1244 on the servo side, and adapt or switch off the monitoring (p1240/p1280, p1284).
Why does my G120 raise F07404?
The G120 manual gives one cause: the Vdc_max monitoring (p1284) responded in U/f control. Check the line supply voltage and the braking module, then adapt p0210 and p1284.
Can I switch the monitoring off so F07404 stops appearing?
Only where it is not needed: set p1240 = 0, on G130/G150 and S120/S150 vector also p1280 = 0. For G120 and G120XA the remedy instead adapts the monitoring via p1284.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals