What it means
F07403 (Drive: Lower DC link voltage threshold reached) means that the DC link voltage monitoring was active and the DC link voltage fell to its lower threshold while the drive was in the Operation
state. The manual describes this code for the G130, G150, S120 and S150. Depending on the drive's configuration, the same condition can also be signalled only as an alarm (A) or without any reaction (N). Issued as a fault, the drive executes OFF1 and the message must be acknowledged immediately before the drive can run again.
Why it appears
The cause is the same in substance for all drive objects; what differs between VECTOR and SERVO drive objects is which parameters configure the monitoring and which threshold is monitored:
- VECTOR drive objects (G130/G150 and S120/S150): the DC link voltage monitoring is active (p1240, p1280 = 5, 6) and the lower DC link voltage threshold (r1246, r1286) was reached in the
Operation
state. - SERVO drive objects: the DC link voltage monitoring is active (p1240 = 5, 6) and the lower DC link voltage threshold (p1248) was reached in the
Operation
state.
What to check
- Check the line supply voltage.
- Check the infeed.
- Adapt the device supply voltage (p0210) or the switch-on level (p1245, p1285). On SERVO drive objects, reduce the lower DC link voltage threshold (p1248) instead.
- Disable the DC link voltage monitoring (p1240 = 0, and p1280 = 0 where this parameter is used).
Parameters the manual names
- p1240 — Vdc controller or Vdc monitoring configuration: the monitoring is active when it is set to 5 or 6, and setting it to 0 switches the monitoring out.
- p1280 — Vdc controller or Vdc monitoring configuration (U/f): the second configuration parameter named in the cause; active at 5 or 6, disabled at 0.
- r1246 — Vdc_min controller switch-in level (kinetic buffering): the lower DC link voltage threshold whose reaching raises the fault on VECTOR drive objects.
- r1286 — Vdc_min controller switch-in level (kinetic buffering) (U/f): the corresponding lower threshold for the U/f configuration.
- p0210 — Drive unit line supply voltage: adapt this setting so it matches the actual line supply voltage.
- p1245 — Vdc_min controller switch-in level (kinetic buffering): the switch-on level you adapt so that the lower threshold is no longer reached during operation.
- p1285 — Vdc_min controller switch-in level (kinetic buffering) (U/f): the corresponding switch-on level for the U/f configuration.
- p1248 — DC link voltage threshold lower: the lower DC link voltage threshold on SERVO drive objects; the remedy is to reduce it.
Acknowledging and restarting
The fault is acknowledged immediately. Once the cause has been corrected and the fault acknowledged, the drive can be restarted. Where the drive's configuration signals the same condition only as an alarm (A) or without any reaction (N), neither a reaction nor an acknowledgement applies.
The same on every family
Every manual that describes F07403 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | OFF1 (NONE, OFF2, OFF3) | IMMEDIATELY | Infeed faulted (13) | None | SINAMICS G130, G150 List Manual · p. 1545 |
| S120, S150 | OFF1 (NONE, OFF2, OFF3) | IMMEDIATELY | Infeed faulted (13) | None | SINAMICS S120, S150 List Manual · p. 2800 |
| S120, S150 | OFF1 (NONE, OFF2, OFF3) | IMMEDIATELY | Infeed faulted (13) | None | SINAMICS S120, S150 List Manual · p. 2799 |
The drives this code lives on
F07403 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07403 mean on a SINAMICS drive?
The DC link voltage monitoring was active and the DC link voltage reached its lower threshold while the drive was in the Operation state. For VECTOR drive objects the threshold is r1246/r1286, for SERVO drive objects it is p1248.
How do I clear fault F07403?
Check the line supply voltage and the infeed, then adapt the device supply voltage (p0210) or the switch-on level (p1245, p1285) — on SERVO drive objects reduce p1248 instead. Afterwards the fault is acknowledged immediately and the drive can be restarted.
Which parameters activate or disable the monitoring behind F07403?
The monitoring is active when p1240 (and, where used, p1280) is set to 5 or 6. Setting p1240 to 0 — and p1280 to 0 where used — switches the monitoring out.
Can F07403 appear without tripping the drive?
Yes. Depending on the drive's configuration the same condition can also be signalled as an alarm (A) or without any reaction (N); in both cases no acknowledgement is required.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F07xxx group · SINAMICS manuals · Siemens manuals