What it means
F01651 means that the synchronization routine of the Safety Integrated function was unsuccessful. The message text SI P1 (CU) places the fault at the Safety Integrated (SI) function of the Control Unit (CU). On the drives with a higher-level control, Safety Integrated must synchronize the safety time slices between the two monitoring channels and between the Control Unit and the higher-level control; the G120 manual describes the same failure as an unsuccessful synchronization of the safety time slices between processor 1 and processor 2. The fault results in a STOP A that cannot be acknowledged.
Why it appears
- The Safety Integrated function requires a synchronization of the safety time slices between the two monitoring channels and between the Control Unit and the higher-level control, and this synchronization routine was unsuccessful.
- On the G120 the equivalent condition is a failed synchronization of the safety time slices between processor 1 and processor 2.
- Which concrete situation ended the synchronization is stored as the fault value in r0949 — see the decoding below; the values 121 and 150 have a defined meaning, every other value is only for internal Siemens troubleshooting.
What to check
- Read the fault value in r0949 and interpret it as a decimal number.
- Fault value 121: carry out a common POWER ON/warm restart for the higher-level control and SINAMICS.
- Fault value 150: check the setting of p9510 (SI Motion isochronous PROFIBUS master) and correct it if required.
- Carry out a POWER ON (switch-off/switch-on) for all components — for the G120 this is the remedy the manual names.
- If the fault persists, upgrade the Motor Module/Hydraulic Module software, upgrade the Control Unit software and upgrade the software of the higher-level control.
Reading the message value
The drive enters the cause of the fault into r0949 as a fault value that must be interpreted as a decimal number. The G120 manual decodes no value of its own — there the fault value is only for internal Siemens troubleshooting.
- 121 — with SINUMERIK Safety Integrated enabled, a drive-side warm restart was performed on the CU/NX; or, with SINUMERIK Safety Integrated enabled, the function
restore factory setting
was selected on a drive object of the CU and a drive-side warm restart was initiated. - 150 — fault in the synchronization to the PROFIBUS master.
- All other values — only for internal Siemens troubleshooting.
Parameters the manual names
- r0949 (fault value): read the value stored here, interpreted as a decimal, to tell which situation triggered F01651.
- p9510 (SI Motion isochronous PROFIBUS master; the G130/G150 manual names it SI Motion clock-cycle synchronous PROFIBUS master): check this setting and correct it if required when the fault value is 150.
Acknowledging and restarting
The fault results in a STOP A that cannot be acknowledged, so it is not cleared from the operator panel in the usual way. The remedy is a POWER ON (switch-off/switch-on) for all components. After a fault value of 121, bring the higher-level control and SINAMICS back up together — a common POWER ON/warm restart for both.
What differs between the drive families
Straight from the manuals' own fields — F01651 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS S120, S150 List Manual · p. 2634 |
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | None | SINAMICS G130, G150 List Manual · p. 1436 |
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Hardware/software error (1) | — | SINAMICS G120 · p. 842 |
The drives this code lives on
F01651 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01651 mean on a SINAMICS drive?
The Safety Integrated function could not synchronize the safety time slices — between the two monitoring channels and the higher-level control (on the G120: between processor 1 and processor 2). The drive goes to a STOP A that cannot be acknowledged.
How do I clear fault F01651?
Carry out a POWER ON (switch-off/switch-on) for all components. If the fault value in r0949 is 121, the higher-level control and SINAMICS must be restarted together with a common POWER ON/warm restart.
What does fault value 150 in F01651 mean?
It indicates a fault in the synchronization to the PROFIBUS master. Check the setting of p9510 (SI Motion isochronous PROFIBUS master) and correct it if required.
What does fault value 121 in F01651 mean?
With SINUMERIK Safety Integrated enabled, a drive-side warm restart was performed on the CU/NX, or the function "restore factory setting" was selected on a drive object of the CU and a drive-side warm restart was initiated.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.