What it means
F01658 is raised by the Safety Integrated monitoring of processor 1 in the Control Unit (SI P1 (CU)) when the selected PROFIsafe telegram does not match the safety configuration. The manuals describe two situations behind the same code: on the G120 the PROFIsafe telegram number in p60022 is not suitable
for the enabled safety functions, while on the G130, G150, S120 and S150 the number differs
— it is set differently in p9611 and p60022. In either case the drive coasts down and may only be restarted once the fault has been acknowledged; the fault itself does not result in a safety stop response.
Why it appears
- Telegram unsuitable (G120): the telegram number entered in p60022 does not suit the Safety functions that have been enabled. If PROFIsafe is not enabled (p9601.3 = 0), it is not permissible to select a PROFIsafe telegram in p60022; if PROFIsafe is enabled (p9601.3 = 1), a PROFIsafe telegram must be selected there.
- F-DIs transferred via PROFIsafe (G120): when the transfer of the F-DIs via PROFIsafe is selected (p9501.30 = 1), telegram 900 must be selected in p60022. This only applies to Control Units which support Extended Functions via PROFIsafe (r9771.4 = 1).
- Telegram numbers differ (G130, G150, S120, S150): the PROFIsafe telegram number is set differently in p9611 and p60022. If p9611 is not equal to 998, the number must be identically set in both parameters. If p9611 = 998 — kept for compatibility with firmware versions < 4.5 — only the values 0 and 30 are permitted in p60022.
What to check
- Read the telegram number in p60022 and select the number that matches the Safety functions that have been enabled.
- On the G120, check whether PROFIsafe is enabled: with p9601.3 = 0 no PROFIsafe telegram may remain selected in p60022; with p9601.3 = 1 a PROFIsafe telegram must be selected there.
- Where the F-DIs are transferred via PROFIsafe (p9501.30 = 1), enter telegram 900 in p60022 — this applies only if the Control Unit supports Extended Functions via PROFIsafe (r9771.4 = 1).
- On the G130, G150, S120 and S150, compare p9611 and p60022 and set the same telegram number in both parameters. When p9611 = 998, restrict p60022 to the values 0 or 30.
Parameters the manual names
- p60022 (PROFIsafe telegram selection): the parameter whose value is corrected here — it must match the enabled safety functions and, except when p9611 = 998, be identical to p9611.
- p9611 (SI PROFIsafe telegram selection (Control Unit)): the Control Unit's own PROFIsafe telegram selection, which must hold the same number as p60022; at p9611 = 998 only 0 and 30 are permitted in p60022.
- p9601 (SI enable functions integrated in the drive (processor 1)): p9601.3 shows whether PROFIsafe is enabled, which decides whether p60022 must or must not contain a PROFIsafe telegram.
- p9501 (SI Motion enable safety functions (processor 1)): p9501.30 = 1 selects the transfer of the F-DIs via PROFIsafe and therefore requires telegram 900 in p60022.
- r9771 (SI common functions (processor 1)): r9771.4 = 1 identifies Control Units that support Extended Functions via PROFIsafe, the condition under which the telegram 900 requirement applies.
Acknowledging and restarting
Correct the telegram configuration first; the fault is then acknowledged by switching the converter power off and on again (POWER ON), and the drive will not restart until this acknowledgment has been made. The manuals note that this fault does not result in a safety stop response.
What differs between the drive families
Straight from the manuals' own fields — F01658 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 844 |
| S120, S150 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2641 |
| G130, G150 | OFF2 | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1442 |
The drives this code lives on
F01658 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01658 mean on a SINAMICS drive?
The Safety Integrated monitoring of processor 1 in the Control Unit reports that the PROFIsafe telegram number does not match the safety configuration — on the G120 the number in p60022 is unsuitable for the enabled safety functions, on the G130, G150, S120 and S150 it differs between p9611 and p60022.
How do I clear fault F01658?
Select in p60022 the telegram number that matches the enabled Safety functions — telegram 900 when the F-DIs are transferred via PROFIsafe — and set the same number in p9611 and p60022 where both parameters apply. Then acknowledge the fault by switching the power off and on again.
Does F01658 trigger a safety stop?
No. The manuals note that this fault does not result in a safety stop response.
Why does p9611 = 998 matter for F01658?
With p9611 = 998, which exists for compatibility with firmware versions < 4.5, only the values 0 and 30 are permitted in p60022, so any other telegram number there leads to the fault.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.