Alarm · SINAMICS G130, G150, S120, S150

A35214TM: Temperature alarm threshold channel 3 exceeded

What it means

A35214 is an alarm from a Terminal Module (TM): the temperature measured through the TM temperature sensing on channel 3 (r4105[3]) has exceeded the alarm threshold set in p4102[6]. As an alarm it signals the condition without tripping the drive. The drive stores the temperature actual value at the moment of initiation in the alarm value r2124 (interpret decimal, in 0.1 °C). Depending on the drive configuration, the same condition can also be output as a fault (F) or with no reaction (N).

Why it appears

  • The temperature measured using the temperature sensing of the Terminal Module (TM) on channel 3 (r4105[3]) has exceeded the threshold value set to initiate this alarm (p4102[6]).

What to check

  1. Read the temperature actually measured on channel 3 in r4105[3] and compare it with the alarm threshold in p4102[6]; the alarm value r2124 holds the temperature actual value at the time of initiation (interpret decimal, in 0.1 °C).
  2. Check the sensor type set in p4100[3]: when a PTC thermistor or a bimetallic NC contact (p4100[3] = 1, 4) is connected, the drive derives the temperature value from the sensor resistance in r4101[3], so read r4101[3] to interpret what is reported.
  3. Allow the temperature sensor to cool down to below p4102[6] - hysteresis (5 K, for TM150, can be set using p4118[3]). The alarm then clears by itself.

Reading the message value

  • Alarm value (r2124, interpret decimal): temperature actual value at the time of initiation, scaled in 0.1 °C.
  • For sensor type PTC thermistor and bimetallic NC contact (p4100[3] = 1, 4): if r4101[3] > 1650 ohms, r4105[3] = 250 °C; if r4101[3] <= 1650 ohms, r4105[3] = -50 °C.

Parameters the manual names

  • r4105[3] — temperature actual value of the Terminal Module temperature sensing on channel 3; shows the temperature that exceeded the threshold.
  • p4102[6] — alarm threshold of channel 3; the alarm is initiated when r4105[3] rises above this value and clears when the temperature falls below it minus the hysteresis.
  • p4100[3] — sensor type of channel 3; the resistance-based evaluation with the fixed values 250 °C and -50 °C applies for PTC thermistor and bimetallic NC contact (p4100[3] = 1, 4).
  • r4101[3] — TM120 sensor resistance; read it when a PTC thermistor or bimetallic NC contact is connected, because the drive derives the reported temperature from it.
  • r2124 — alarm value; contains the temperature actual value at the time of initiation, to be interpreted decimal in 0.1 °C.
  • p4118[3] — TM150 threshold hysteresis; on a TM150 the 5 K hysteresis below p4102[6] can be set here.

Acknowledging and restarting

The alarm needs no acknowledgement. It goes by itself once the temperature sensor has cooled down to below p4102[6] minus the hysteresis (5 K; on a TM150 settable in p4118[3]). If the drive is configured to issue the same condition as a fault (F), the fault is acknowledged immediately via POWER ON; as the no-reaction variant (N) no acknowledgement is required either.

The same on every family

Every manual that describes A35214 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3216
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1884

The drives this code lives on

A35214 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35214 in SINAMICS mean?

A Terminal Module has measured a temperature on its channel 3 above the alarm threshold in p4102[6]; the measured value is in r4105[3]. Depending on the drive configuration, the same condition can also appear as a fault or with no reaction.

How do I reset alarm A35214?

Let the temperature sensor cool down to below p4102[6] minus the hysteresis (5 K, on a TM150 settable via p4118[3]); the alarm then clears by itself. If the condition is configured as a fault, acknowledge it immediately via POWER ON.

Why does A35214 show 250 °C or -50 °C?

For a PTC thermistor or bimetallic NC contact (p4100[3] = 1, 4) the temperature value is derived from the resistance in r4101[3]: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.

Which parameter sets the alarm threshold for A35214?

p4102[6] holds the channel 3 alarm threshold; the hysteresis below it is 5 K, settable on a TM150 in p4118[3].

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.