What it means
A35214 is an alarm from a Terminal Module (TM): the temperature measured through the TM temperature sensing on channel 3 (r4105[3]) has exceeded the alarm threshold set in p4102[6]. As an alarm it signals the condition without tripping the drive. The drive stores the temperature actual value at the moment of initiation in the alarm value r2124 (interpret decimal, in 0.1 °C). Depending on the drive configuration, the same condition can also be output as a fault (F) or with no reaction (N).
Why it appears
- The temperature measured using the temperature sensing of the Terminal Module (TM) on channel 3 (r4105[3]) has exceeded the threshold value set to initiate this alarm (p4102[6]).
What to check
- Read the temperature actually measured on channel 3 in r4105[3] and compare it with the alarm threshold in p4102[6]; the alarm value r2124 holds the temperature actual value at the time of initiation (interpret decimal, in 0.1 °C).
- Check the sensor type set in p4100[3]: when a PTC thermistor or a bimetallic NC contact (p4100[3] = 1, 4) is connected, the drive derives the temperature value from the sensor resistance in r4101[3], so read r4101[3] to interpret what is reported.
Allow the temperature sensor to cool down to below p4102[6] - hysteresis (5 K, for TM150, can be set using p4118[3]).
The alarm then clears by itself.
Reading the message value
- Alarm value (r2124, interpret decimal): temperature actual value at the time of initiation, scaled in 0.1 °C.
- For sensor type PTC thermistor and bimetallic NC contact (p4100[3] = 1, 4): if r4101[3] > 1650 ohms, r4105[3] = 250 °C; if r4101[3] <= 1650 ohms, r4105[3] = -50 °C.
Parameters the manual names
- r4105[3] — temperature actual value of the Terminal Module temperature sensing on channel 3; shows the temperature that exceeded the threshold.
- p4102[6] — alarm threshold of channel 3; the alarm is initiated when r4105[3] rises above this value and clears when the temperature falls below it minus the hysteresis.
- p4100[3] — sensor type of channel 3; the resistance-based evaluation with the fixed values 250 °C and -50 °C applies for PTC thermistor and bimetallic NC contact (p4100[3] = 1, 4).
- r4101[3] — TM120 sensor resistance; read it when a PTC thermistor or bimetallic NC contact is connected, because the drive derives the reported temperature from it.
- r2124 — alarm value; contains the temperature actual value at the time of initiation, to be interpreted decimal in 0.1 °C.
- p4118[3] — TM150 threshold hysteresis; on a TM150 the 5 K hysteresis below p4102[6] can be set here.
Acknowledging and restarting
The alarm needs no acknowledgement. It goes by itself once the temperature sensor has cooled down to below p4102[6] minus the hysteresis (5 K; on a TM150 settable in p4118[3]). If the drive is configured to issue the same condition as a fault (F), the fault is acknowledged immediately via POWER ON; as the no-reaction variant (N) no acknowledgement is required either.
The same on every family
Every manual that describes A35214 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3216 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1884 |
The drives this code lives on
A35214 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A35214 in SINAMICS mean?
A Terminal Module has measured a temperature on its channel 3 above the alarm threshold in p4102[6]; the measured value is in r4105[3]. Depending on the drive configuration, the same condition can also appear as a fault or with no reaction.
How do I reset alarm A35214?
Let the temperature sensor cool down to below p4102[6] minus the hysteresis (5 K, on a TM150 settable via p4118[3]); the alarm then clears by itself. If the condition is configured as a fault, acknowledge it immediately via POWER ON.
Why does A35214 show 250 °C or -50 °C?
For a PTC thermistor or bimetallic NC contact (p4100[3] = 1, 4) the temperature value is derived from the resistance in r4101[3]: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.
Which parameter sets the alarm threshold for A35214?
p4102[6] holds the channel 3 alarm threshold; the hysteresis below it is 5 K, settable on a TM150 in p4118[3].
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.