Alarm · SINAMICS G130, G150, S120, S150

A35211TM: Temperature alarm threshold channel 0 exceeded

What it means

A35211 comes from a Terminal Module (TM): the temperature acquired through its temperature sensing, channel 0 (r4105[0]), has risen above the alarm threshold set in p4102[0]. Depending on how the drive is configured, the same condition can also be output as a fault (F) or as a message without a reaction (N) instead of the alarm.

Why it appears

  • The temperature measured using the temperature sensing of the Terminal Module (TM) — value r4105[0] — has exceeded the threshold value in p4102[0] that initiates this alarm.

What to check

  1. Compare the temperature currently measured via the Terminal Module's temperature sensing (r4105[0]) with the alarm threshold p4102[0].
  2. Allow the temperature sensor to cool down to below p4102[0] minus the hysteresis — the hysteresis is 5 K, and on a TM150 it can be set using p4118[0].
  3. If the sensor is a PTC thermistor or a bimetallic NC contact (p4100[0] = 1, 4), read the sensor resistance in r4101[0]: a resistance above 1650 ohms corresponds to 250 °C, one of 1650 ohms or less to -50 °C.

Reading the message value

  • Alarm value (r2124, interpret decimal): the temperature actual value at the time the alarm was initiated, in 0.1 °C.
  • For sensor type "PTC thermistor" and "Bimetallic NC contact" (p4100[0] = 1, 4):
    • r4101[0] > 1650 ohms: r4105[0] = 250 °C
    • r4101[0] <= 1650 ohms: r4105[0] = -50 °C

Parameters the manual names

  • r4105[0] — temperature actual value of the Terminal Module's temperature sensing, channel 0; read it to see the measured temperature.
  • p4102[0] — alarm threshold of channel 0; the alarm comes when r4105[0] rises above it, and clears again below this value minus the hysteresis.
  • p4100[0] — sensor type of channel 0; 1 is a PTC thermistor, 4 a bimetallic NC contact, and for these types the resistance determines the displayed temperature.
  • r4101[0] — sensor resistance (parameter name: TM120 sensor resistance); read it for PTC thermistor and bimetallic NC contact sensors to interpret the displayed temperature.
  • r2124 — alarm value; interpreted as a decimal number it holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.
  • p4118[0] — TM150 hysteresis of the alarm/fault threshold; sets how far below p4102[0] the temperature must fall before the message clears.

Acknowledging and restarting

No acknowledgement is needed: the drive does not intervene in operation on this alarm, and it clears by itself once the temperature at the sensor falls below p4102[0] minus the hysteresis. If the drive is configured to output the condition as a fault (F) instead, the manual specifies acknowledgement IMMEDIATELY (POWER ON).

The same on every family

Every manual that describes A35211 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3215
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1883

The drives this code lives on

A35211 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35211 mean on a SINAMICS drive?

A Terminal Module (TM) has measured a temperature through its temperature sensing channel 0 (r4105[0]) that is above the alarm threshold set in p4102[0]. Depending on the configuration, the same condition can also be output as a fault (F) or as a message without a reaction (N).

How do I clear A35211?

No acknowledgement is required. Let the temperature sensor cool down below p4102[0] minus the hysteresis (5 K; on a TM150 settable via p4118[0]) and the message clears by itself.

Where can I see the temperature that triggered A35211?

The alarm value r2124, interpreted as a decimal number, holds the temperature actual value at the time the alarm was initiated, in 0.1 °C. The currently measured temperature is in r4105[0].

Why does the Terminal Module show 250 °C or -50 °C?

With sensor type PTC thermistor or bimetallic NC contact (p4100[0] = 1, 4), the drive maps the resistance r4101[0] to a fixed temperature: more than 1650 ohms gives 250 °C, 1650 ohms or less gives -50 °C.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.