Alarm · SINAMICS G130, G150, S120, S150

A35213TM: Temperature alarm threshold channel 2 exceeded

What it means

A35213 is reported by a Terminal Module (TM) when the temperature measured through its temperature sensing on channel 2 — the value in r4105[2] — has risen above the alarm threshold stored in p4102[4]. The drive does not react to this alarm; it only signals that the threshold was crossed. Depending on how the drive is configured, the same condition can also be output as a fault (F) or as a message with no reaction (N).

For the sensor types "PTC thermistor" and "Bimetallic NC contact" (p4100[2] = 1, 4), the following applies: if r4101[2] is greater than 1650 ohms, then r4105[2] = 250 °C; if r4101[2] is 1650 ohms or less, then r4105[2] = -50 °C.

Why it appears

  • The temperature that the Terminal Module (TM) picks up through its temperature sensing, shown in r4105[2], has risen above the threshold in p4102[4] at which this alarm is initiated.

What to check

  1. Read the temperature the Terminal Module is currently measuring on channel 2 in r4105[2].
  2. Allow the temperature sensor to cool down until the temperature is below p4102[4] minus the hysteresis — 5 K; on a TM150 the hysteresis can be set using p4118[2].

Reading the message value

  • Alarm value in r2124, interpreted as a decimal number: the temperature actual value at the time the alarm was initiated, given in 0.1 °C.

Parameters the manual names

  • r4105 — temperature actual value of the Terminal Module's channel-2 temperature sensing; read it to see the temperature currently being measured.
  • p4102 — alarm threshold of channel 2; the alarm initiates when the measured temperature exceeds it, and the sensor must cool below this threshold minus the hysteresis.
  • p4100 — sensor type of channel 2; the special 250 °C / -50 °C readings apply when it is set to 1 ("PTC thermistor") or 4 ("Bimetallic NC contact").
  • r4101 — sensor resistance of the TM120; with a "PTC thermistor" or "Bimetallic NC contact", more than 1650 ohms gives 250 °C and 1650 ohms or less gives -50 °C.
  • r2124 — alarm value; for this alarm it holds the temperature actual value at the time of initiation in 0.1 °C (interpret decimal).
  • p4118 — hysteresis of the fault/alarm threshold on the TM150; use it to set the hysteresis instead of the fixed 5 K.

Acknowledging and restarting

The alarm requires no acknowledgement. Let the temperature sensor cool down until the temperature is below p4102[4] minus the hysteresis (5 K; on a TM150 the hysteresis can be set using p4118[2]). If the drive is configured to output the condition as a fault (F) instead, it is acknowledged IMMEDIATELY (POWER ON).

The same on every family

Every manual that describes A35213 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3216
G130, G150NONENONEExternal measured value / signal state outside the permissible range (16)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1883

The drives this code lives on

A35213 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35213 mean on a SINAMICS drive?

A Terminal Module (TM) has measured a temperature on its channel 2 sensing input, r4105[2], that is above the alarm threshold in p4102[4]. The drive takes no action; it only signals that the threshold was exceeded.

How do I clear alarm A35213?

No acknowledgement is needed. Let the temperature sensor cool down until the temperature is below p4102[4] minus the hysteresis (5 K; on a TM150 you can set the hysteresis in p4118[2]).

Why does A35213 show 250 °C or -50 °C?

With the sensor types "PTC thermistor" or "Bimetallic NC contact" (p4100[2] = 1, 4), r4105[2] reads 250 °C when r4101[2] > 1650 ohms and -50 °C when r4101[2] <= 1650 ohms, so the value only takes these two readings.

Where can I see the temperature at which A35213 was triggered?

In the alarm value r2124, interpreted as a decimal number: it holds the temperature actual value at the time the alarm was initiated, in 0.1 °C.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.