Alarm · SINAMICS S120, S150

A35226TM: Tracks A/B are deactivated

What it means

A35226 reports that there is no frequency setpoint for the Terminal Module 41 (TM41). Because that setpoint is missing, the output of tracks A/B has been held (frozen). The manual lists five situations that lead to this on an S120 or S150, ranging from a missing interconnection at connector input p4420 to a TM41 that is not connected to DRIVE-CLiQ.

Why it appears

  • The interconnection of connector input p4420 is missing, so no setpoint reaches the TM41.
  • The leading encoder is not in the ready state — for example a parking encoder is active or the encoder data set is not parameterized.
  • The TM41 itself has a fault.
  • The TM41 is in the commissioning mode (p0010 > 0).
  • The TM41 component is not connected to DRIVE-CLiQ.

What to check

  1. Interconnect connector input p4420 appropriately so that the TM41 again receives its setpoint.
  2. Bring the leading encoder into the ready state; check whether a parking encoder is still active or the encoder data set is not parameterized.
  3. Check p0010: while the TM41 is in the commissioning mode (p0010 > 0) the tracks stay frozen, so end commissioning (p0010 = 0).
  4. Check that the TM41 component is connected to DRIVE-CLiQ.
  5. Diagnose the TM41 and remove any TM41 faults.

Parameters the manual names

  • p4420 — CI: TM41 encoder emulation position setpoint (Enc_emul s_set). For this alarm, check that this connector input is interconnected; a missing interconnection is the first cause the manual names.
  • p0010 — Drive commissioning parameter filter (Drv com par_filt). For this alarm, the TM41 counts as being in the commissioning mode whenever p0010 > 0, so confirm the value is 0 before looking for a hardware cause.

The same on every family

Every manual that describes A35226 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Application/technological function faulted (17)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3219

The drives this code lives on

A35226 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35226 mean on a SINAMICS S120 or S150?

It means there is no frequency setpoint for the Terminal Module 41 (TM41), so the output of tracks A/B has been held (frozen).

Why does A35226 appear?

The manual names five causes: connector input p4420 not interconnected, the leading encoder not in the "ready" state, a TM41 fault, the TM41 in the commissioning mode (p0010 > 0), or the TM41 component not connected to DRIVE-CLiQ.

How do I fix A35226?

Interconnect connector input p4420 appropriately, bring the leading encoder into the "ready" state and remove any TM41 faults. Also finish commissioning (p0010 = 0) and make sure the TM41 is connected to DRIVE-CLiQ.

Which parameters matter for A35226?

p4420, the CI: TM41 encoder emulation position setpoint, must be interconnected. p0010 matters because the commissioning mode (p0010 > 0) freezes the tracks.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A35xxx group · SINAMICS manuals · Siemens manuals