What it means
A35081 is a TM54F alarm that watches the failsafe digital input (F-DI) belonging to safe acknowledgment. It is raised when the F-DI configured in p10006 has been at a logical 1 signal for more than 10 seconds although no acknowledgment for safe acknowledgment was performed at that input. When no safe acknowledgment is taking place, the F-DI must sit at a steady logical 0 signal: the drive insists on this so that a safety-relevant acknowledgment — or the "Internal Event Acknowledge" signal — cannot be triggered unintentionally, for example if a wire breaks or one of the two digital inputs bounces. Depending on how the drive is configured, the same condition can also be output as fault F35081 instead of as this alarm.
Why it appears
- The F-DI configured in p10006 carries a logical 1 signal for more than 10 seconds.
- No acknowledgment was performed for safe acknowledgment at the F-DI, so a steady logical 0 signal is required there; the steady 1 would risk an unintentional safety-relevant acknowledgment (or the "Internal Event Acknowledge" signal) — exactly what this monitoring is there to prevent, e.g. when a wire breaks or one of the two digital inputs bounces.
What to check
- Check whether a safe acknowledgment was actually performed at the F-DI configured in p10006. If none was performed, the input must be at a steady logical 0 — a logical 1 present for more than 10 seconds is precisely what the alarm reports.
- Set the failsafe digital input (F-DI) to a logical 0 signal (p10006), so the input is back at the steady 0 the drive requires whenever no safe acknowledgment is being performed.
Parameters the manual names
- p10006 — "SI Motion acknowledgment internal event F-DI (processor 1)": selects the failsafe digital input that triggers the internal event for safe acknowledgment. It is the input this alarm monitors, and the remedy is to bring the input configured here back to logical 0.
Acknowledging and restarting
The condition is cleared by restoring the required signal state: bring the F-DI configured in p10006 back to a steady logical 0. As an alarm, A35081 requires no acknowledgment and goes once the input sits at logical 0 again. If the drive's configuration raises the same condition as fault F35081 instead, that fault causes no automatic drive reaction but must be acknowledged immediately once the F-DI has been returned to logical 0.
The same on every family
Every manual that describes A35081 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | Terminal Module (TM) | SINAMICS S120, S150 List Manual · p. 3209 |
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | Terminal Module (TM) | SINAMICS G130, G150 List Manual · p. 1878 |
The drives this code lives on
A35081 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A35081 on a SINAMICS drive mean?
It is a TM54F alarm: the failsafe digital input (F-DI) configured in p10006 for safe acknowledgment has been at logical 1 for more than 10 seconds although no safe acknowledgment was performed at it.
How do I clear A35081?
Set the F-DI configured in p10006 back to a steady logical 0 signal. As an alarm it needs no acknowledgment; only if the same condition is output as fault F35081 must it be acknowledged immediately.
Why must the F-DI sit at logical 0?
So that no safety-relevant acknowledgment (or the "Internal Event Acknowledge" signal) can be triggered unintentionally — for example if a wire breaks or one of the two digital inputs bounces.
Which parameter belongs to A35081?
p10006 — the SI Motion acknowledgment internal event F-DI (processor 1), which selects the failsafe digital input that the alarm monitors.
Codes next to this one