Alarm · SINAMICS G130, G150, S120, S150

A35075TM54F: Error during internal communication

What it means

A35075 reports that the Terminal Module 54F (TM54F) has run into an error in its internal communication. The manual points to two configuration situations that produce this alarm even when nothing is physically wrong: the TM54F master and the TM54F slave must carry identical settings in p10000 (the TM54F communication clock cycle) and in p10010 (the TM54F drive object assignment). Depending on how the drive is configured, the same condition can also be output as a fault; the description below covers both variants.

Why it appears

  • The TM54F has registered an error in its internal data exchange.
  • p10000 (TM54F master) and p10000 (TM54F slave) hold different values.
  • p10010 (TM54F master) and p10010 (TM54F slave) hold different values.

What to check

  1. Compare the TM54F master against the TM54F slave. If p10000 or p10010 differ, launch the copy function that transfers the node identifier onto the TM54F by setting p9700 = 1D hex.
  2. Use p9701 = EC hex so the TM54F accepts the changed SI motion data and the hardware CRC is acknowledged.
  3. Store the complete parameter set by writing 1 to p0977.
  4. Carry out a POWER ON (switch-off/switch-on) for all components — the preceding steps only take effect after this power cycle.
  5. If the parameters already match, the alarm points at a genuine communication problem: review how the electrical cabinet is laid out and how the cables are routed, with attention to EMC.
  6. Install a current software version on the TM54F.
  7. If the alarm keeps recurring, contact Technical Support.
  8. As the final option, replace the TM54F.

Reading the message value

  • The drive writes an alarm value into r2124, which the manual says to read as a decimal number. It is reserved for internal Siemens diagnostics, so it carries no meaning a technician can act on.

Parameters the manual names

  • p10000 — TM54F communication clock cycle: check that master and slave are set alike; a mismatch triggers this alarm.
  • p10010 — TM54F drive object assignment: check that master and slave are set alike; a mismatch triggers this alarm.
  • p9700 — set to 1D hex to launch the node-identifier copy function on the TM54F.
  • p9701 — set to EC hex to acknowledge the changed SI motion data and the hardware CRC on the TM54F.
  • p0977 — set to 1 to save all parameters after the copy and CRC steps.
  • r2124 — alarm value, read as a decimal number; internal Siemens diagnostics only.

Acknowledging and restarting

The parameter steps only become effective once every component has been switched off and switched on again. If the drive outputs the condition as a fault instead of the alarm, this same power cycle is the immediate way to clear it — simply acknowledging on the panel is not enough.

The same on every family

Every manual that describes A35075 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEHardware/software error (1)Terminal Module (TM)SINAMICS S120, S150 List Manual · p. 3208
G130, G150NONENONEHardware/software error (1)Terminal Module (TM)SINAMICS G130, G150 List Manual · p. 1877

The drives this code lives on

A35075 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A35075 mean on a SINAMICS G130, G150, S120 or S150?

It reports an internal communication error in the Terminal Module TM54F. The alarm is also raised when p10000 or p10010 are not set identically on the TM54F master and the TM54F slave.

How do I clear A35075 after a p10000 or p10010 mismatch?

Start the node-identifier copy function with p9700 = 1D hex, acknowledge the hardware CRC with p9701 = EC hex, save all parameters with p0977 = 1, and then switch all components off and on again.

What is the alarm value in r2124 for A35075?

It is a decimal number reserved for internal Siemens diagnostics. The manual gives no further meaning that a technician could use.

Why does A35075 keep coming back although the parameters match?

Then it indicates a real internal communication problem: review the cabinet layout and cable routing for EMC, update the TM54F software, and if it persists contact Technical Support or replace the TM54F.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.