Alarm · SINAMICS G130, G150, S120, S150

A32401Encoder 2: Alarm threshold zero mark failed

What it means

A32401 is the Encoder 2 zero mark alarm. The drive monitors how far Encoder 2 travels between zero marks: once more than 1.5 times the parameterized zero mark distance has passed without a zero mark being detected, the alarm threshold is exceeded and the drive raises A32401. The zero mark distance used for this monitoring is the one set in p0425 (rotary encoder) or p0424 (linear encoder). Depending on the drive's configuration, the same condition can also be issued as a fault (F) or with no reaction at all (N). How many increments have been counted since POWER ON or since the last detected zero mark is stored as the alarm value in r2124.

Why it appears

  • The 1.5 x parameterized zero mark distance was exceeded without a zero mark being detected.
  • The zero mark distance being monitored is the one set in p0425 (rotary encoder) or p0424 (linear encoder).

What to check

  1. Check that the encoder cables are routed in compliance with EMC.
  2. Check the plug connections.
  3. Check the encoder type — the encoder must have equidistant zero marks.
  4. Adapt the parameter for the clearance between zero marks (p0425).
  5. Replace the encoder or the encoder cable.

Reading the message value

  • The alarm value can be read in r2124; interpret the value as a decimal number.
  • It contains the number of increments after POWER ON or since the last zero mark that was detected.
  • 4 increments correspond to 1 encoder pulse.

Parameters the manual names

  • p0425 (Encoder rotary zero mark distance): sets the zero mark distance monitored for Encoder 2 when a rotary encoder is connected; the remedy includes adapting this clearance between zero marks.
  • p0424 (Encoder linear zero mark distance): sets the same monitoring distance when a linear encoder is connected.
  • r2124 (Alarm value): read the counted increments here, interpreted as a decimal number, while the alarm is present.

Acknowledging and restarting

As an alarm, A32401 triggers no automatic response from the drive and needs no acknowledgement — the drive keeps running. If the drive is configured to raise the same condition as a fault (F), the fault must be acknowledged IMMEDIATELY; by default the drive also takes no automatic action on the fault, and IASC/DCBRK, OFF1, OFF2, OFF3 or STOP2 can be set as the fault response depending on the drive object. When the condition is issued with no reaction (N), the drive takes no action and nothing has to be acknowledged.

The same on every family

Every manual that describes A32401 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS S120, S150 List Manual · p. 3102
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 2SINAMICS G130, G150 List Manual · p. 1780

The drives this code lives on

A32401 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A32401 mean on a SINAMICS drive?

Encoder 2 has traveled further than 1.5 times the zero mark distance set in p0425 (rotary encoder) or p0424 (linear encoder) without a zero mark being detected. The counted increments are stored as the alarm value in r2124.

Does A32401 stop the drive?

No. As an alarm the drive takes no automatic action and no acknowledgement is required. If the condition is configured as a fault instead, it must be acknowledged IMMEDIATELY.

Which parameters matter for A32401?

p0425 sets the zero mark distance for a rotary encoder and p0424 for a linear encoder; the alarm trips at 1.5 times this distance. The alarm value with the counted increments can be read in r2124.

What does the value of A32401 tell me?

Interpreted as a decimal number, it is the number of increments counted after POWER ON or since the last zero mark that was detected, where 4 increments equal 1 encoder pulse.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A32xxx group · SINAMICS manuals · Siemens manuals