What it means
Encoder 2 signals that the zero mark distance measured at the encoder does not correspond to the zero mark distance parameterized in the drive — the alarm threshold of the zero mark monitoring has been exceeded. For distance-coded encoders the zero mark distance is determined from pairs of detected zero marks; depending on how these pairs are generated, a single missing zero mark does not necessarily result in a fault and then has no effect in the system. The zero mark distance used by the monitoring is set in p0425 (rotary encoder) or p0424 (linear encoder). Depending on the drive configuration, the same condition can also be issued as a fault (F) or as a message without a reaction (N).
Why it appears
- The zero mark distance measured at Encoder 2 does not correspond to the zero mark distance parameterized in the drive (p0424 for a linear encoder, p0425 for a rotary encoder).
What to check
- Check that the encoder cables are routed in compliance with EMC.
- Check the plug connections.
- Check the encoder type (encoder with equidistant zero marks).
- Adapt the parameterized distance between the zero marks (p0424, p0425).
- Replace the encoder or the encoder cable.
Reading the message value
- The message value is the alarm value, which the drive also stores in r2124.
- Interpret r2124 as a decimal number: it contains the last measured zero mark distance in increments, where 4 increments correspond to 1 encoder pulse.
- The sign of the value designates the direction of motion when the zero mark distance was detected.
Parameters the manual names
- p0424 — Encoder linear zero mark distance: holds the parameterized zero mark distance for a linear encoder; adapt it here if the measured distance differs.
- p0425 — Encoder rotary zero mark distance: the same setting for a rotary encoder.
- r2124 — Alarm value: read the alarm value here as a decimal number to see the last measured zero mark distance in increments.
Acknowledging and restarting
As an alarm, A32400 requires no acknowledgement; the drive does not react to the message itself, it only points to the mismatch between the measured and the parameterized zero mark distance. Only when the drive is configured to issue the same condition as a fault (F) is an immediate acknowledgement required.
What differs between the drive families
Straight from the manuals' own fields — A32400 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | — | — | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS S120, S150 List Manual · p. 3101 |
| G130, G150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS G130, G150 List Manual · p. 1779 |
The drives this code lives on
A32400 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A32400 mean?
Encoder 2 measures a zero mark distance that does not match the distance parameterized in p0424 (linear encoder) or p0425 (rotary encoder), so the alarm threshold of the zero mark monitoring has been exceeded. The drive takes no action on the alarm itself.
How do I fix alarm A32400?
Check that the encoder cables are routed in compliance with EMC, check the plug connections, and verify the encoder type. Then adapt the parameterized distance between zero marks in p0424 or p0425; if the alarm persists, replace the encoder or the encoder cable.
What does the value of A32400 tell me?
The alarm value in r2124, interpreted as a decimal number, holds the last measured zero mark distance in increments, with 4 increments equal to 1 encoder pulse. The sign designates the direction of motion when the zero mark distance was detected.
Do I have to acknowledge A32400?
No — as an alarm it needs no acknowledgement. If the drive is configured to raise the same condition as a fault (F) instead, that fault requires an immediate acknowledgement.