Alarm · SINAMICS G115D, G120, G120C, G120XA, G130, G150, S120, S150

A08511PN/COMM BOARD: Receive configuration data invalid

What it means

A08511 is issued by the PROFINET interface — titled PN/COMM BOARD: Receive configuration data invalid on S120, S150, G130 and G150, and PROFINET: Receive configuration data invalid on G120 and G120XA — because the drive unit did not accept the receive configuration data, i.e. the cyclic telegram configuration with which the controller addresses the drive. The message value is a placeholder; the concrete result of the configuration check stands in r2124 and is interpreted as a decimal number. Depending on the drive's configuration, the same condition can also be output as a fault. On G115D and G120C the manual prints the code only in a short table, without the detailed value breakdown given for the other families.

Why it appears

  • The receive configuration data sent by the controller does not fit the drive: the wrong drive objects or sequence for process data exchange (p0978), more PZD data words for output or input than a drive object — or the overall device — provides, or an uneven number of bytes for input or output.
  • Cyclic operation is not active, or the setting data for synchronization was not accepted.
  • On a CBE20 Shared Device, the configuration of the F-CPU has been changed.
  • Clock synchronization or PROFIsafe is set up incorrectly for a PZD interface (p8815[0], p8815[1], p8839), a PROFIsafe parameter such as F_dest is wrong, or the PROFIsafe connection is rejected while no isochronous connection exists.

What to check

  1. Read the alarm value in r2124 (interpret it as a decimal number); it names exactly which configuration check failed.
  2. Value 1 or 2: check the list of drive objects with process data exchange (p0978). Note that with p0978[x] = 0, that entry and every drive object after it in the list drop out of the process data exchange.
  3. Value 2: compare the number of PZD data words for output and input per drive object with the indices available in r2050/p2051 (PZD IF1) and r8850/p8851 (PZD IF2). Value 257 (S120, S150): do the same check for the complete device.
  4. Value 3: check that input and output each carry an even number of bytes, so the telegrams on the controller side match the drive.
  5. Value 4: the setting data for synchronization was not accepted — the manual refers here to A01902 for more information.
  6. Value 17: unplug and plug the A-CPU again (CBE20 Shared Device after a change of the F-CPU configuration).
  7. Values 223 and 500: check the setting in p8839 and p8815, and ensure that only one PZD interface is operated in clock synchronism or with PROFIsafe.
  8. Value 501: check the PROFIsafe address set in p9610. Value 502 (G120): check the enable of F-DI (p9501.30).
  9. Value 503: the PROFIsafe connection stays rejected until an isochronous connection exists (p8969).

Reading the message value

r2124 holds the return value of the receive configuration data check:

  • 1 — the connection was set up to more drive objects than the device is configured for; the objects exchanging process data, and their sequence, are defined in p0978.
  • 2 — the telegram carries more PZD data words for output or input than the drive object accepts; the possible count follows from the indices of r2050/p2051 (PZD IF1) and r8850/p8851 (PZD IF2).
  • 3 — uneven number of bytes for input or output.
  • 4 — setting data for synchronization not accepted (details under A01902).
  • 5 — cyclic operation not active.
  • 17 — CBE20 Shared Device: the configuration of the F-CPU has been changed.
  • 223 — the clock synchronization of the PZD interface set in p8815[0] is not permissible.
  • 257 (S120, S150) — PN Shared Device: more PZD data words for output or input than the overall device accepts.
  • 500 — the PROFIsafe configuration of the interface set in p8815[1] is not permissible.
  • 501 — a PROFIsafe parameter is wrong, for example F_dest.
  • 502 (G120) — the PROFIsafe telegram does not match.
  • 503 — the PROFIsafe connection stays rejected until an isochronous connection exists (p8969).

Values beyond this list are reserved for internal Siemens troubleshooting.

Parameters the manual names

  • r2124 — holds the alarm value of this message; read it in decimal to identify the rejected check.
  • p0978 — the list of drive objects exchanging process data, in order; correct it for alarm values 1 and 2 (an entry of 0 ends the exchange list).
  • r2050 / p2051 — PZD receive and send words of PZD IF1; their index count is the word limit per drive object behind alarm value 2.
  • r8850 / p8851 — the same limit for the second interface, PZD IF2.
  • p8815 — selects the function of each PZD interface; index [0] concerns clock synchronization and index [1] PROFIsafe, checked for alarm values 223 and 500.
  • p8839 — assigns the PZD interfaces to the hardware; checked together with p8815 for alarm values 223 and 500.
  • p8969 — PROFIsafe wait for clock synchronization; named with alarm value 503, where the PROFIsafe connection waits for the isochronous connection.
  • p9610 — the PROFIsafe address of the Control Unit; verify it when the alarm value is 501.
  • p9501 — the enable of the F-DI (p9501.30) is checked here when the alarm value is 502 on G120.

Acknowledging and restarting

As an alarm, the message clears itself once the corrected receive configuration data has been transferred and the cyclic connection matches the drive again. If the drive is configured so that the same condition is output as a fault, the affected drive objects are switched off, and that fault must be acknowledged immediately before the converter can be restarted.

What differs between the drive families

Straight from the manuals' own fields — A08511 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2919
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1634
G120NONENONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 898
G120XANONENONESINAMICS G120XA PN converter · p. 1148
G115DSINAMICS G115D distributed drive · p. 395
G120CSINAMICS G120C Converters · p. 386

The drives this code lives on

A08511 is described for G115D, G120, G120C, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A08511 in SINAMICS mean?

The PROFINET interface did not accept the receive configuration data with which the controller addresses the drive. The return value of the configuration check in r2124 shows exactly which part did not fit.

How do I clear A08511?

Correct the receive configuration data so it matches the drive: p0978 for the drive object list, the PZD word counts per object, and for clock synchronization or PROFIsafe the settings p8815, p8839 and p9610. The alarm then goes away by itself.

What does alarm value 2 of A08511 tell me?

That a drive object is given more PZD data words for output or input than it provides indices for (r2050/p2051, or r8850/p8851 for the second interface). Check the telegram length configured for that object.

Can A08511 also appear as a fault?

Yes — depending on the drive's configuration, the same condition can also be output as a fault. The affected drive objects are then switched off, and the fault must be acknowledged immediately before a restart.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.