A06301Infeed: Line supply overvoltage

What it means

A06301 (Infeed: Line supply overvoltage) is reported by the infeed when the filtered (steady-state) value of the rms line supply voltage Vrms rises above the overvoltage alarm threshold. The threshold is not an absolute voltage: the drive compares Vrms with the factor p0281 multiplied by the set line supply voltage p0210 — Vrms > p0281 * p0210. The message value carries the line supply voltage, and the drive also stores the actual steady-state value in r2124 as a floating-point alarm value. Depending on the drive configuration, the same condition can also be output as a fault (F06301).

Why it appears

  • The filtered (steady-state) value of the rms line supply voltage Vrms is higher than the alarm threshold: Vrms > p0281 * p0210.
  • Because the threshold is calculated from p0210 and p0281 rather than set as a fixed voltage, a mismatch between these settings and the actual supply triggers the same message.

What to check

  1. Check the line supply.
  2. Check the line supply voltage setting p0210 against the actual supply.
  3. Check the alarm threshold p0281.
  4. Read the actual steady-state line supply voltage in r2124 and compare it with the threshold p0281 * p0210.

Reading the message value

  • Message value: Line supply voltage: %1 — the message carries the line supply voltage.
  • The actual steady-state line supply voltage is stored as the alarm value in r2124, as a floating-point number.

Parameters the manual names

  • p0210 (Drive unit line supply voltage / U_connect) — the line supply voltage the unit is configured for; the overvoltage threshold is derived from it, so verify it against the actual supply when A06301 appears.
  • p0281 (Line supply overvoltage alarm threshold / U_l_over A thr) — the threshold factor; the alarm trips when the steady-state rms voltage exceeds p0281 * p0210, so check it if the supply itself is within its normal range.
  • r2124 (Alarm value) — read the actual steady-state line supply voltage here; the drive stores it as a floating-point number.

Acknowledging and restarting

As an alarm, A06301 needs no acknowledgment: it goes away by itself once the filtered rms line supply voltage falls back below the threshold. If the drive is configured to output the same condition as fault F06301, the drive does not trip automatically and the fault can be acknowledged immediately (the manual also names acknowledgment after POWER ON for the fault case).

The same on every family

Every manual that describes A06301 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONENetwork fault (2)NoneSINAMICS S120, S150 List Manual · p. 2764
G130, G150NONENONENetwork fault (2)NoneSINAMICS G130, G150 List Manual · p. 1528

The drives this code lives on

A06301 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A06301 mean on a SINAMICS?

The infeed has measured a filtered (steady-state) rms line supply voltage above the overvoltage alarm threshold — the condition is Vrms > p0281 * p0210. It is an alarm and does not stop the drive.

How do I fix A06301?

Check the line supply, then verify that the line supply voltage setting p0210 matches the actual supply and that the alarm threshold p0281 is set appropriately. The actual steady-state voltage can be read in r2124 and compared with the threshold p0281 * p0210.

Does A06301 have to be acknowledged?

No — as an alarm it needs no acknowledgment and clears itself once the voltage is back below the threshold. If the condition is output as fault F06301, it can be acknowledged immediately.

Where can I see the voltage that triggered A06301?

In the message value (Line supply voltage: %1) and in r2124, where the drive stores the actual steady-state line supply voltage as a floating-point number.