What it means
A06206 is the line-current symmetry monitoring of the infeed: it responds when the asymmetry of the three line currents at the terminals of the power unit exceeds the alarm threshold set in p3465. In parallel, the drive signals a possible phase failure via bit 2 of status parameter r3405 (r3405.2). Depending on how the drive is configured, the same condition can also be issued as fault F06206.
Why it appears
- The line supply voltage is asymmetrical, or a line phase has failed — for example because a fuse has ruptured or a terminal connection has become loose.
- Cyclic power fluctuations in the DC link with the line frequency can also result in unequal rms values of the line currents; for this type of operating scenario, the manual recommends deactivating the monitoring by setting p3465[0] = 0 and p3465[3] = 0.
What to check
- Check the line supply, the terminals and the fuses.
- Check the line supply quality and the system fault level.
- Check the load.
- Check the settings in p3462 (infeed phase failure detection times) and p3465 (infeed current symmetry monitoring thresholds).
Reading the message value
- The drive stores the alarm value as a floating-point number in r2134.
- Digits to the left of the decimal point: highest rms phase current in amps.
- Decimal places: quotient of the lowest and the highest rms phase current value.
Parameters the manual names
- p3465 — infeed current symmetry monitoring thresholds: the alarm threshold this code responds to; setting p3465[0] = 0 and p3465[3] = 0 deactivates the monitoring.
- p3462 — infeed phase failure detection times: check this setting together with p3465 as part of the remedy.
- r2134 — alarm value for float values: read here the highest rms phase current (digits left of the decimal point) and the ratio of lowest to highest rms phase current (decimal places).
Acknowledging and restarting
As an alarm, A06206 does not force the drive out of its operating state and requires no acknowledgment: once the three line currents are balanced again and remain within the threshold in p3465, the alarm goes away by itself. If the drive raises the condition as fault F06206 instead, the fault must be acknowledged before it is deleted — immediate acknowledgment is sufficient, a POWER ON is not required. Because the code itself does not switch the drive off, no special restart sequence is needed once the line supply has been restored to a symmetric state.
The same on every family
Every manual that describes A06206 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Network fault (2) | None | SINAMICS S120, S150 List Manual · p. 2759 |
The drives this code lives on
A06206 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A06206 on a SINAMICS infeed mean?
The line-current symmetry monitoring has responded: the asymmetry of the three line currents at the terminals of the power unit exceeds the alarm threshold in p3465. The usual causes are line voltage asymmetry or failure of a line phase, e.g. a ruptured fuse or a loose terminal connection.
How do I fix alarm A06206?
Check the line supply, the terminals and the fuses, then the line supply quality and system fault level, and finally the load. The alarm clears by itself once the currents are balanced again; if the condition is configured as fault F06206, that fault must be acknowledged immediately.
Can I switch off the line current symmetry monitoring?
Yes — for cyclic power fluctuations in the DC link with the line frequency the manual recommends deactivating the monitoring with p3465[0] = 0 and p3465[3] = 0. Also review the thresholds in p3465 and the detection times in p3462.
What does the alarm value r2134 show for A06206?
The digits left of the decimal point give the highest rms phase current in amps, and the decimal places give the quotient of the lowest and highest rms phase current value.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A06xxx group · SINAMICS manuals · Siemens manuals