Alarm · SINAMICS S120, S150

A06260Infeed: Temperature in the line filter too high

What it means

A06260 reports that the temperature monitoring inside the line filter has responded. The manual restricts this function to an Active Interface Module (AIM): on other filter types the temperature monitoring does not exist. The alarm itself does not intervene in drive operation and does not need to be acknowledged, but if the excessive temperature persists over the complete monitoring time, the drive raises fault F06261 instead.

Why it appears

  • The temperature monitoring in the line filter has tripped because the filter has become too warm.
  • If the temperature remains too high for the whole monitoring time, the condition escalates into fault F06261.

What to check

  1. Compare the line filter type set in p0220[0] with the filter that is actually connected. Either connect the filter specified for the infeed in use, or correct the setting of the filter type in p0220[0].
  2. Temperature monitoring is mandatory for AIM line filters: make sure the filter's temperature switch is correctly and reliably wired to input X21 of the infeed.
  3. Reduce the ambient temperature around the line filter.
  4. Relieve the load on the infeed and on the filter module.
  5. Check how large the line supply voltage actually is.
  6. If the internal fan of the filter module is defective, replace the fan.
  7. If the temperature switch of the filter module is defective, replace the filter module.

Parameters the manual names

  • p0220 — the connected line filter type is set here (index [0]); for this alarm, verify that this setting matches the filter physically present and correct it if it does not.

Acknowledging and restarting

As an alarm, A06260 does not force a drive reaction and requires no acknowledgement before restart; it clears once the condition at the filter is removed. If the temperature stays too high for the entire monitoring time, the drive instead raises fault F06261, whose handling is described on its own page.

The same on every family

Every manual that describes A06260 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONELine filter faulted (15)Power ModuleSINAMICS S120, S150 List Manual · p. 2763

The drives this code lives on

A06260 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A06260 mean on a SINAMICS S120 or S150?

The temperature monitoring in the line filter has responded. This monitoring exists only for an Active Interface Module, and if the temperature stays too high for the whole monitoring time, the alarm turns into fault F06261.

Does A06260 have to be acknowledged?

No. The alarm does not intervene in drive operation and needs no acknowledgement, but the underlying temperature problem should be fixed before it escalates into fault F06261.

What should I check first for A06260?

Compare the line filter type set in p0220[0] with the filter actually connected, and make sure the filter's temperature switch is correctly and reliably wired to input X21 of the infeed.

Why does the temperature monitoring not exist on my line filter?

The manual states that the temperature monitoring is only available for an Active Interface Module (AIM) line filter, whose temperature switch must be connected to input X21 of the infeed.