Alarm · SINAMICS S120, S150

A06215Infeed: Summation current too high

What it means

The infeed monitors the smoothed total of its phase currents (i1 + i2 + i3). A06215 appears when this total becomes greater than 3 % of the maximum power unit current (r0209). Possible backgrounds: a ground fault in the DC link that results in a high summation current, a zero point calibration of the current measurement that was not carried out, or defective current measurement in the power unit. Depending on the drive configuration, the same condition is not only raised as this alarm but can also be issued as a fault (F06215).

Why it appears

  • A ground fault in the DC link results in a high summation current (r0069.6). The manual warns: The DC component in the line currents can damage/destroy the power unit, line reactor or line filter!
  • The zero point calibration of the current measurement was not carried out — the drive references p3491 and alarm A06602 here.
  • The current measurement in the power unit is defective.

What to check

  1. Check the DC link for a low-ohmic or high-ohmic ground fault and, if one is present, remove it.
  2. Increase the monitoring time of the current offset measurement (p3491).
  3. Replace the power unit if necessary.

Reading the message value

  • Alarm value r2124 (floating point): the smoothed total of the phase currents — i.e. the value that exceeded 3 % of r0209.

Parameters the manual names

  • r0209 (PU I_max): maximum power unit current — the 3 % threshold of this alarm refers to it.
  • r0069: the cause points to r0069.6, where the high summation current produced by a DC-link ground fault shows up.
  • p3491 (INF I_offs t_mon): monitoring time of the infeed current offset measurement — the remedy for this alarm is to increase it.
  • r2124: alarm value — holds the smoothed total of the phase currents in floating point.

Acknowledging and restarting

As an alarm, A06215 needs no acknowledgement: it clears itself once the smoothed total of the phase currents drops back below 3 % of the maximum power unit current (r0209) — for example after the DC-link ground fault has been removed. Depending on the configuration, the drive can also raise the condition as fault F06215; the reaction to that fault is none by default, with OFF1 or OFF2 selectable, and the fault is acknowledged immediately — acknowledgement via POWER ON is also possible. Only in that fault variant is an acknowledgement needed before the infeed runs again.

The same on every family

Every manual that describes A06215 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEGround fault / inter-phase short-circuit detected (7)Power ModuleSINAMICS S120, S150 List Manual · p. 2761

The drives this code lives on

A06215 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does A06215 on a SINAMICS S120 or S150 mean?

The infeed has detected that the smoothed total of the phase currents (i1 + i2 + i3) exceeds 3 % of the maximum power unit current (r0209). The manual names a DC-link ground fault, a missing zero point calibration of the current measurement, or defective current measurement in the power unit as possible causes.

Does A06215 have to be acknowledged?

No — as an alarm it clears itself once the summation current falls back below the threshold. If the drive is configured to raise the condition as fault F06215 instead, acknowledge it immediately or via POWER ON before restarting.

How do I fix A06215?

Check the DC link for a low-ohmic or high-ohmic ground fault and remove it if present, and increase the monitoring time of the current offset measurement (p3491). Replace the power unit if necessary.

Where can I see the current that triggered A06215?

In the alarm value r2124, which holds the smoothed total of the phase currents as a floating point number.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.