What it means
A02150 appears when the system was not able to load an application or a technology extension. On the G130, G150, S120 and S150 the manual prints the title TEC: Technology Extension cannot be loaded
; on the G120 and G120XA the same alarm number carries the title OA: Application cannot be loaded
, where OA stands for Open Architecture. Which condition prevented the loading is reported as an alarm value in r2124, which the manual says to interpret hexadecimal. Abbreviations used below: TEC = Technology Extension, DCB = Drive Control Block, DCC = Drive Control Chart.
Why it appears
- The system was not able to load a Technology Extension (TEC variants on G130, G150, S120, S150) or an OA application (G120, G120XA).
- Alarm value 10 hex (16 dec): the interface version in the DCB user library is not compatible to the DCC standard library that has been loaded. The G120/G120XA manual prints this value simply as 16.
- Alarm value 12 hex (18 dec): a technology package was not able to be downloaded to a Control Unit because the required warm restart could not be performed. This value is listed for the TEC variants only.
- Every manual entry for this code adds the note:
Only for internal Siemens troubleshooting
.
What to check
- Read the alarm value in r2124 (interpret hexadecimal) to see which condition is present.
- For value 10 hex (16 dec) — printed as 16 on the G120/G120XA: load a DCB user library that is compatible to the interface of the DCC standard library that has been loaded.
- For value 12 hex (18 dec): carry out a POWER ON (switch-off/switch-on) for all components.
- The TEC variants additionally list a warm restart with p0009 = 30 and p0976 = 2 or 3.
- Carry out a POWER ON (switch-off/switch-on) for all components.
- Upgrade the firmware to a later version.
- Contact Technical Support.
Reading the message value
- 10 hex (16 dec) — the interface version in the DCB user library is not compatible to the DCC standard library that has been loaded. On the G120/G120XA the same condition is printed as value 16.
- 12 hex (18 dec) — a technology package was not able to be downloaded to a Control Unit because the required warm restart could not be performed (listed for the TEC variants).
Parameters the manual names
- r2124 (alarm value): read the alarm value here — interpreting hexadecimal — to identify which condition triggered A02150.
- p0009 (device commissioning parameter filter): set to 30 as part of the warm restart listed for the TEC variants.
- p0976 (reset and load all parameters): set to 2 or 3, together with p0009 = 30, to carry out that warm restart.
- r4950, r4955, p4956, r4957: the TEC DO-specific number, identifier, activation and version, which the manual cross-references under See also for this alarm.
Acknowledging and restarting
No acknowledgement is required for this alarm. The manual describes no separate reset: clearing A02150 means removing the cause with the steps in the checklist above — loading a compatible DCB user library, a warm restart and/or a POWER ON of all components, a firmware upgrade — with contacting Technical Support as the remaining step it names.
What differs between the drive families
Straight from the manuals' own fields — A02150 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | NONE | Hardware/software error (1) | None | SINAMICS G130, G150 List Manual · p. 1510 |
| S120, S150 | NONE | NONE | Hardware/software error (1) | None | SINAMICS S120, S150 List Manual · p. 2735 |
| G120 | NONE | NONE | Hardware/software error (1) | — | SINAMICS G120 · p. 866 |
| G120XA | — | NONE | — | — | SINAMICS G120XA PN converter · p. 1114 |
The drives this code lives on
A02150 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A02150 mean?
The drive was not able to load a Technology Extension (TEC) or, on the G120/G120XA, an OA (Open Architecture) application. The alarm value in r2124 shows which condition prevented the loading.
How do I fix A02150?
Load a DCB user library compatible to the interface of the loaded DCC standard library, carry out a warm restart (p0009 = 30, p0976 = 2, 3) and/or a POWER ON of all components, and upgrade the firmware. If the condition remains, the manual's last step is contacting Technical Support.
What does alarm value 10 hex (16 dec) in A02150 mean?
That the interface version in the DCB user library is not compatible to the DCC standard library that has been loaded. The remedy is to load a compatible DCB user library.
Does A02150 have to be acknowledged?
No — this alarm requires no acknowledgement. You clear it by removing the cause with the remedy steps.