Alarm · SINAMICS G120, G130, G150, S120, S150

A02096MTrace 0: cannot be saved

What it means

The drive cannot save the measurement results of a multiple trace on the memory card (trace recorder 0). The multiple trace is therefore not started at all or is canceled while it runs. The message value (%1) carries the alarm value, which the drive also writes to r2124 and which identifies the concrete reason for the alarm.

Why it appears

  • The memory card cannot be accessed — the card is not inserted, or access to it is blocked by a mounted USB drive (alarm value 1).
  • The data save operation is too slow — a second trace has completed before the measurement results of the first trace could be saved, or writing the measurement result files to the card is blocked by a parameter save (alarm value 3).
  • The data save operation was canceled — for instance, the file required for the data save operation could not be found (alarm value 4).

What to check

  1. Insert or remove the memory card — the card may be missing, or a mounted USB drive may be blocking access to it.
  2. Use a larger memory card.
  3. Configure a longer trace time or use an endless trace.
  4. Avoid saving parameters while a multiple trace is running.
  5. Check whether other functions are presently accessing the measurement result files.

Reading the message value

  • The alarm value is stored in r2124 and is to be interpreted as a decimal number; the message value %1 contains this value.
  • 1 — memory card cannot be accessed: the card is not inserted or is blocked by a mounted USB drive.
  • 3 — data save operation too slow: a second trace has been completed before the measurement results of the first trace were able to be saved, or writing the measurement result files to the card is blocked by the parameter save.
  • 4 — data save operation canceled: for instance, the file required for the data save operation was not able to be found.

Parameters the manual names

  • r2124 — alarm value: read it as a decimal number to see which of the three situations (1, 3 or 4) triggered the alarm.
  • p4840 — MTrace cycle number setting: the parameter the manual cross-references for this alarm; it sets the cycle number of the multiple trace.

Acknowledging and restarting

No acknowledgment is required: the alarm goes away by itself once the measurement results can be saved again — for example after the memory card has been inserted or freed. The multiple trace can then be started again.

What differs between the drive families

Straight from the manuals' own fields — A02096 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1508
S120, S150Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2733
G120NONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 864

The drives this code lives on

A02096 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A02096 (MTrace 0: cannot be saved) mean on a SINAMICS drive?

The drive could not save the measurement results of a multiple trace on the memory card (trace recorder 0), so the multiple trace is not started or is canceled.

How do I fix A02096?

Insert or remove the memory card, use a larger card if necessary, configure a longer trace time or an endless trace, avoid saving parameters while the multiple trace runs, and check that no other function is currently accessing the measurement result files.

Where can I read the exact reason for A02096?

In the alarm value r2124, interpreted as a decimal number: 1 means the memory card cannot be accessed, 3 that the save operation is too slow, and 4 that the save operation was canceled.

Does A02096 have to be acknowledged?

No — the alarm clears itself once the measurement results can be saved again; the multiple trace can then be started again.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.