What it means
A02098 (MTrace 1: cannot be saved) is raised when the drive cannot save the measurement results of a multiple trace from trace recorder 1 on the memory card; the multiple trace is then not started or is canceled. The alarm concerns the trace function only. An alarm value in r2124 tells which of the three saving problems occurred.
Why it appears
- The measurement results of a multiple trace on trace recorder 1 cannot be saved on the memory card, so the multiple trace is not started or is canceled.
- Which situation applies is stored as an alarm value in r2124 (interpret decimal): 1 — the memory card cannot be accessed; 3 — the data save operation is too slow; 4 — the data save operation was canceled.
What to check
- Read the alarm value in r2124 (interpret decimal) to see which of the three situations applies.
- Insert or remove the memory card.
- Use a larger memory card.
- Configure a longer trace time or use an endless trace.
- Avoid saving parameters while a multiple trace is running.
- Check whether other functions are presently accessing measurement result files.
Reading the message value
- The drive stores an alarm value in r2124; interpret it decimal.
- 1: Memory card cannot be accessed — card is not inserted or is blocked by a mounted USB drive.
- 3: Data save operation too slow — a second trace has been completed before the measurement results of the first trace were able to be saved, or writing the measurement result files to the card is blocked by the parameter save.
- 4: Data save operation canceled — for instance, the file required for the data save operation was not able to be found.
Parameters the manual names
- r2124 — alarm value: read it decimal to determine whether the memory card cannot be accessed (1), the data save operation is too slow (3) or was canceled (4).
- p4840 — MTrace cycle number setting: the cycle number of the multiple trace; the manual names this parameter in connection with this alarm.
Acknowledging and restarting
This alarm needs no acknowledgement, so there is nothing to reset at the drive. Remove the cause — the memory card must be inserted and accessible, it must have enough capacity, and no parameter save or other function may block the measurement result files while the trace runs — and then start the multiple trace again.
What differs between the drive families
Straight from the manuals' own fields — A02098 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2734 |
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1509 |
| G120 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 865 |
The drives this code lives on
A02098 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does alarm A02098 in SINAMICS mean?
It means the measurement results of a multiple trace (trace recorder 1) could not be saved on the memory card, so the multiple trace was not started or was canceled.
Why does A02098 appear although a memory card is inserted?
The alarm value in r2124 distinguishes the causes: value 3 means the data save operation was too slow — for example a second trace finished before the first results were saved, or a parameter save blocked the files — and value 4 means the save operation was canceled, for instance because a required file was not found.
How do I fix A02098?
Insert or remove the memory card, use a larger card, configure a longer trace time or an endless trace, avoid saving parameters while the multiple trace is running, and check whether other functions are presently accessing the measurement result files.
Does A02098 have to be acknowledged?
No. The alarm requires no acknowledgement; remove the cause and start the multiple trace again.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the A02xxx group · SINAMICS manuals · Siemens manuals