Fault · SINAMICS G130, G150, S120, S150

F36207Hub: Overtemperature component

What it means

F36207 means that the temperature on the DRIVE-CLiQ Hub Module has exceeded the fault threshold; the drive raises the message locally for this component. The same condition can, depending on the drive's configuration, also be signalled only as an alarm (A) or as a message with no reaction at all (N) instead of a fault.

Why it appears

  • The temperature measured on the DRIVE-CLiQ Hub Module is above the component's fault threshold.

What to check

  1. Check the ambient temperature at the installation location of the component.
  2. Replace the component involved (the DRIVE-CLiQ Hub Module).

Reading the message value

  • The drive enters the actual temperature into the message value. Read it in r0949 and interpret the value as a decimal number: it shows the actual temperature in 0.1 °C resolution.

Parameters the manual names

  • r0949 — fault value: read the decimal value here to see the actual Hub temperature that triggered F36207, given in 0.1 °C resolution.

Acknowledging and restarting

The overtemperature condition itself does not cause the drive to switch off, so once the cause is removed — the ambient temperature at the installation location is acceptable, or the Hub Module has been replaced — the drive can be restarted. The fault is acknowledged immediately; switching the power on (POWER ON) also acknowledges it. In the alarm (A) and no-reaction (N) variants no acknowledgement is required.

The same on every family

Every manual that describes F36207 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONE (OFF1, OFF2)IMMEDIATELY (POWER ON)Overtemperature of the electronic components (6)Terminal Board (TB)SINAMICS S120, S150 List Manual · p. 3249
G130, G150NONE (OFF1, OFF2)IMMEDIATELY (POWER ON)Overtemperature of the electronic components (6)Terminal Board (TB)SINAMICS G130, G150 List Manual · p. 1911

The drives this code lives on

F36207 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F36207 mean on a SINAMICS drive?

It reports that the temperature on the DRIVE-CLiQ Hub Module has exceeded the fault threshold. Depending on the drive configuration, the same condition can also appear only as an alarm (A) or as a message with no reaction (N).

How do I see the actual temperature that triggered F36207?

Read the fault value in r0949 and interpret it as a decimal number. The value shows the actual temperature with a resolution of 0.1 °C.

How is F36207 fixed?

Check the ambient temperature at the installation location of the component. If the message persists, replace the component involved, the DRIVE-CLiQ Hub Module.

Does F36207 shut the drive down?

No, in none of its variants (fault, alarm A, no reaction N) does the drive take an automatic switch-off action. The fault variant is acknowledged immediately, and switching the power on also acknowledges it.