Fault · SINAMICS G130, G150, S120, S150

F32130Encoder 2: Zero mark and position error from the coarse synchronization

What it means

Encoder 2 reports this fault when, after the pole position has been initialized — via track C/D, Hall signals or the pole position identification routine — the zero mark is detected outside the permissible angular range, so fine synchronization is not carried out. How much deviation the drive accepts depends on the initialization path, and the fault value shows the position actually found. Depending on the drive configuration, the same condition can also be issued only as an alarm or without any reaction.

Why it appears

  • The pole position was initialized using track C/D, Hall signals or the pole position identification routine, and the zero mark was then detected outside the permissible range.
  • With initialization via track C/D (p0404) the drive checks whether the zero mark occurs in an angular range of +/-18 ° mechanical.
  • With initialization via Hall sensors (p0404) or pole position identification (p1982) it checks whether the zero mark occurs in an angular range of +/-60 ° electrical.
  • For distance-coded encoders, the test is carried out after passing 2 zero marks.
  • Fine synchronization was not carried out.

What to check

  1. Check that the encoder cables are routed in compliance with EMC.
  2. Check the plug connections.
  3. If the Hall sensor is used as an equivalent for track C/D, check the connection.
  4. Check the connection of track C or D.
  5. Replace the encoder or encoder cable.

Reading the message value

  • The message value holds the angular deviation, electrical: %1, and the angle, mechanical: %2.
  • The fault value (r0949) is to be interpreted hexadecimal as yyyyxxxx hex.
  • yyyy: determined mechanical zero mark position (can only be used for track C/D).
  • xxxx: deviation of the zero mark from the expected position as electrical angle; scaling: 32768 dec = 180 °.

Parameters the manual names

  • p0404 — shows the effective encoder configuration, i.e. whether the zero-mark check behind this fault runs via track C/D or via the Hall signals.
  • p1982 — selects the pole position identification; when this routine initializes the pole position, the drive expects the zero mark within +/-60 ° electrical.
  • r0949 — read the fault value here as hexadecimal yyyyxxxx: the determined mechanical zero mark position and its deviation from the expected position as electrical angle.

Acknowledging and restarting

Rectify the cause first: the drive accepts the acknowledgment only while the pulses are inhibited, and once acknowledged the drive can be powered up again. When the condition is configured to appear as an alarm or without a reaction, it does not stop the drive and requires no acknowledgment.

What differs between the drive families

Straight from the manuals' own fields — F32130 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2) Hla: OFF1 (NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 2SINAMICS S120, S150 List Manual · p. 3092
G130, G150OFF1 (IASC/DCBRK, NONE, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 2SINAMICS G130, G150 List Manual · p. 1773

The drives this code lives on

F32130 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F32130 mean?

Encoder 2's zero mark was detected outside the permissible angular range after the pole position was initialized via track C/D, Hall signals or the pole position identification routine, so fine synchronization was not carried out.

Which zero-mark tolerances apply for F32130?

With initialization via track C/D (p0404) the zero mark must occur within +/-18 ° mechanical; via Hall sensors (p0404) or pole position identification (p1982) within +/-60 ° electrical. Distance-coded encoders are tested after passing 2 zero marks.

How do I fix fault F32130?

Check that the encoder cables are routed in compliance with EMC, check the plug connections, the Hall sensor connection if it substitutes track C/D, and the connection of track C or D. If the fault persists, replace the encoder or encoder cable, then acknowledge and restart.

What does the F32130 fault value in r0949 contain?

Interpreted hexadecimal as yyyyxxxx: yyyy is the determined mechanical zero mark position (only usable for track C/D) and xxxx is the deviation of the zero mark from the expected position as electrical angle, where 32768 dec = 180 °.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.