What it means
F32103 tells you that the amplitude of the zero-mark signal — track R — of Encoder 2 lies outside the tolerance bandwidth. The manuals print two titles for the same condition: “Encoder 2: Signal level zero track (track R) outside tolerance” and “Encoder 2: Amplitude error track R”. The drive initiates the fault when the unipolar voltage level at RP/RN is exceeded or when the differential amplitude is undershot: the response thresholds of the unipolar signal levels are < 1400 mV and > 3500 mV, and the response threshold for the differential signal level is < -1600 mV. Note that the drive only evaluates the signal level when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1). Depending on the drive configuration, the same condition can also be issued as an alarm (A) or as a message without reaction (N).
Why it appears
- The zero mark signal level (track R) does not lie within the tolerance bandwidth for Encoder 2.
- The fault is initiated when the unipolar voltage level (RP/RN) is exceeded or if the differential amplitude is undershot.
What to check
- Check the speed range — the frequency characteristic (amplitude characteristic) of the measuring equipment may not be sufficient for the speed range being run.
- Check that the encoder cables and shielding are routed in compliance with EMC.
- Check the plug connections and contacts of the encoder cable.
- Check the encoder type — the encoder must be one with zero marks.
- Check whether the zero mark is connected and that the signal cables RP and RN are connected correctly, not connected with the incorrect polarity.
- Replace the encoder cable.
- If the coding disk is soiled or the lighting has aged, replace the encoder.
Reading the message value
- The message value reads “R track: %1”; %1 is the signal level of track R.
- Fault value in r0949, interpreted hexadecimal: yyyyxxxx hex, where yyyy = 0 and xxxx = the signal level of track R (16 bits with sign).
- For orientation: a signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
- The analog value of the amplitude error is not measured at the same time as the hardware fault output by the Sensor Module, so the fault value can only be represented between -32768 ... 32767 dec (-770 ... 770 mV).
- The signal level is only evaluated when both conditions are satisfied: Sensor Module properties available (r0459.31 = 1) and monitoring active (p0437.31 = 1).
Parameters the manual names
- r0949 — fault value: read the measured signal level of track R here, as the low word xxxx of the hexadecimal value.
- r0459 — Sensor Module properties extended: bit 31 shows whether the Sensor Module properties are available; the signal level for this fault is only evaluated when r0459.31 = 1.
- p0437 — Sensor Module configuration extended: bit 31 must be 1 so that the track R monitoring that raises this fault is active.
Acknowledging and restarting
Once the cause has been eliminated, acknowledge the fault message at the operator panel or in the commissioning tool; the drive does not resume operation until the fault has been acknowledged. If the condition has been configured as an alarm (A) or as a message without reaction (N), the manuals specify neither a reaction nor an acknowledgement for these variants.
What differs between the drive families
Straight from the manuals' own fields — F32103 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Servo: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Vector: OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) Hla: OFF1 (NONE, OFF2, OFF3) | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS S120, S150 List Manual · p. 3083 |
| G130, G150 | OFF1 (IASC/DCBRK, NONE, OFF2, OFF3) | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 2 | SINAMICS G130, G150 List Manual · p. 1765 |
The drives this code lives on
F32103 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F32103 mean on SINAMICS G130, G150, S120 or S150?
The drive has detected that the amplitude of the zero-mark signal (track R) on Encoder 2 lies outside the tolerance bandwidth — either the unipolar voltage level at RP/RN is exceeded or the differential amplitude is undershot.
At which signal levels does the drive trigger F32103?
The response thresholds of the unipolar signal levels are < 1400 mV and > 3500 mV, and the threshold for the differential signal level is < -1600 mV. As a reference, a signal level of 500 mV peak value corresponds to 5333 hex = 21299 dec in r0949.
How do I fix and clear F32103?
Work through the manual's checks: speed range and amplitude characteristic of the measuring equipment, EMC-compliant routing of the encoder cables, plug connections and contacts, encoder type with zero marks, correct RP/RN connection without incorrect polarity, then replace the encoder cable and, if the coding disk is soiled or the lighting aged, the encoder. Afterwards acknowledge the fault message.
Why does the fault value of F32103 look clipped or odd?
Because the analog value of the amplitude error is not measured at the same time as the hardware fault output by the Sensor Module, the fault value in r0949 can only be represented between -32768 ... 32767 dec, i.e. -770 ... 770 mV.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F32xxx group · SINAMICS manuals · Siemens manuals