What it means
The drive monitors the signal level of the zero mark (track R) of Encoder 1. The manuals print the condition under two titles — “Signal level zero mark (track R) outside tolerance” and “Amplitude error track R” — but describe the same monitoring: the fault is raised when the amplitude of the zero-mark/reference track signal (track R) no longer lies within the tolerance bandwidth. This happens either when the unipolar voltage level (RP/RN) is exceeded or when the differential amplitude is undershot.
The response thresholds of the unipolar signal levels of the encoder are between < 1400 mV and > 3500 mV; the response threshold for the differential signal level is < -1600 mV. Depending on the drive configuration, the same condition can also be issued as an alarm (A) or with no reaction (N); in both of those cases there is no reaction and no acknowledgement.
Why it appears
- The zero-mark signal level (track R) of Encoder 1 does not lie within the tolerance bandwidth.
- The unipolar voltage level (RP/RN) is exceeded, or the differential amplitude is undershot.
What to check
- Check the speed range — the frequency characteristic (amplitude characteristic) of the measuring equipment may not be sufficient for the speed range used.
- Check that the encoder cables and shielding are routed in compliance with EMC.
- Check the plug connections and contacts of the encoder cable.
- Check the encoder type — an encoder with zero marks must be used.
- Check that the zero mark is connected and that the signal cables RP and RN are connected correctly, not with reversed polarity.
- Replace the encoder cable.
- If the coding disk is soiled or the lighting is aged, replace the encoder.
Reading the message value
- The message value is “R track: %1”. In r0949, interpreted hexadecimal, the fault value is yyyyxxxx hex: yyyy = 0, and xxxx is the signal level of track R (16 bits with sign).
- A signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
The analog value of the amplitude error is not measured at the same time with the hardware fault output by the Sensor Module.
The fault value can therefore only be represented between -32768 ... 32767 dec (-770 ... 770 mV).- The signal level is only evaluated when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1).
Parameters the manual names
- r0949 — fault value; read it in hexadecimal to obtain the track R signal level.
- r0459 — Sensor Module properties: bit 31 must read 1 (properties available) before the signal level is evaluated at all.
- p0437 — Sensor Module configuration: bit 31 = 1 activates the monitoring of the signal level.
- p0491 — motor encoder fault response ENCODER; the manual references this parameter for how the drive responds to this fault.
Acknowledging and restarting
As a fault, F31103 is acknowledged with PULSE INHIBIT: the drive's pulses must be inhibited before the acknowledgement is accepted; once acknowledged, the drive can be restarted. When the same condition is configured as an alarm (A) or with no reaction (N), no acknowledgement is required.
What differs between the drive families
Straight from the manuals' own fields — F31103 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | Infeed: NONE Servo: ENCODER (IASC/DCBRK, NONE) Vector: ENCODER (IASC/DCBRK, NONE) Hla: ENCODER (NONE) | PULSE INHIBIT | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS S120, S150 List Manual · p. 3026 |
| G130, G150 | Vector: ENCODER (IASC/DCBRK, NONE) Infeed: NONE | PULSE INHIBIT | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS G130, G150 List Manual · p. 1717 |
The drives this code lives on
F31103 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F31103 mean on a SINAMICS drive?
The signal level of the zero mark (track R) of Encoder 1 lies outside the tolerance bandwidth — the unipolar level at RP/RN is exceeded or the differential amplitude is undershot. The same condition can also be output as an alarm or with no reaction.
Which signal levels trigger F31103?
The response thresholds of the unipolar signal levels lie between < 1400 mV and > 3500 mV, and the differential signal level responds below -1600 mV. A 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
How do I decode the fault value of F31103 in r0949?
Interpret r0949 hexadecimal: yyyy = 0 and xxxx is the track R signal level as a 16-bit signed number. The value can only span -32768 ... 32767 dec, i.e. -770 ... 770 mV.
How is F31103 acknowledged and cleared?
As a fault it is acknowledged with PULSE INHIBIT: inhibit the pulses, acknowledge, then restart the drive. In the alarm or no-reaction configuration, no acknowledgement is required.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.