Fault · SINAMICS G130, G150, S120, S150

F31117Encoder 1: Inversion error signals A/B/R

What it means

F31117 reports that on Encoder 1 the evaluation of a square-wave encoder (bipolar, double ended) no longer sees the complementary signals A*, B* and R* as inverted images of A, B and R. The manuals for the G130, G150, S120 and S150 describe this fault alike. Depending on how the drive is configured, the same condition can also be output as an alarm or with no reaction instead of a fault.

For the SMC30 with article number 6SL3055-0AA00-5CA0 or 6SL3055-0AA00-5CA1, for the CUA32 and for the CU310-2 (CU310 in the second manual), the note adds a second situation that raises this fault: a square-wave encoder without track R is in use while track monitoring (p0405.2 = 1) is activated.

Why it appears

  • For a square-wave encoder (bipolar, double ended), the signals A*, B* and R* are not applied inverted with respect to the signals A, B and R.
  • On the SMC30 with article number 6SL3055-0AA00-5CA0 or 6SL3055-0AA00-5CA1, on the CUA32 and on the CU310-2/CU310: a square-wave encoder without track R is used while track monitoring (p0405.2 = 1) is activated.

What to check

  1. Check the encoder and its cable.
  2. Confirm that the encoder actually outputs the signals together with the associated inverted signals (A* against A, B* against B, R* against R).
  3. If the encoder is connected through one of the SMC30 article numbers listed above, check the setting of p0405: p0405.2 = 1 is only possible when the encoder is connected at X520.
  4. If the square-wave encoder has no track R, set the jumpers at the encoder terminal: pin 10 (reference signal R) with pin 7 (encoder power supply, ground), and pin 11 (reference signal R inverted) with pin 4 (encoder power supply). The terminal is X520 on the SMC30, X220 on the CUA32 and X23 on the CU310-2; the second manual additionally places the CUA32 jumpers at X23.

Reading the message value

The drive puts the fault cause into the message value in binary and also holds it in r0949. The manual decodes it bit by bit:

  • Bits 0 ... 15: only for internal Siemens troubleshooting.
  • Bit 16: error track A.
  • Bit 17: error track B.
  • Bit 18: error track R.

Parameters the manual names

  • r0949 — fault value: read it in binary for this fault; bit 16, bit 17 or bit 18 names the failed track A, B or R.
  • p0405 — square-wave encoder track A/B: its bit .2 is the track monitoring that raises this fault when no track R is wired; with the listed SMC30 versions, p0405.2 = 1 is only permissible at X520.
  • p0491 — motor encoder fault response ENCODER: sets how the drive reacts when this encoder fault occurs; the manual cross-refers to it directly under this fault.

Acknowledging and restarting

Once the cause has been removed, the fault is cleared by an immediate acknowledgement. Where the drive is configured to output the same condition only as an alarm or with no reaction, the manual specifies no acknowledgement for it.

What differs between the drive families

Straight from the manuals' own fields — F31117 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: NONE Servo: ENCODER (IASC/DCBRK, NONE) Vector: ENCODER (IASC/DCBRK, NONE) Hla: ENCODER (NONE)Actual position/speed value incorrect or not available (11)Encoder 1SINAMICS S120, S150 List Manual · p. 3031
G130, G150Vector: ENCODER (IASC/DCBRK, NONE) Infeed: NONEIMMEDIATELYActual position/speed value incorrect or not available (11)Encoder 1SINAMICS G130, G150 List Manual · p. 1721

The drives this code lives on

F31117 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F31117 mean in SINAMICS drives?

On Encoder 1 the drive has detected that the inverted signals A*, B* and R* of a square-wave encoder (bipolar, double ended) are not inverted against A, B and R. On specific SMC30 versions, the CUA32 and CU310-2 it also appears when an encoder without track R runs with track monitoring (p0405.2 = 1) activated.

Which track triggered F31117?

Read the fault value in r0949 as binary: bit 16 means track A, bit 17 track B and bit 18 track R. Bits 0 to 15 are reserved for internal Siemens troubleshooting.

How do I fix F31117?

Check the encoder and its cable and confirm that the signals arrive together with their inverted counterparts; on the listed SMC30 versions verify p0405 and, for an encoder without track R, bridge pin 10 to pin 7 and pin 11 to pin 4 at the encoder terminal. Then acknowledge the fault immediately.

Why does F31117 occur even though my encoder has no R track?

Because track monitoring (p0405.2 = 1) is activated while the square-wave encoder has no reference track. Check the p0405 setting or set the jumpers the manual specifies for encoders without track R: pin 10 to pin 7 and pin 11 to pin 4.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.