F31118Encoder 1: Speed change not plausible

What it means

F31118 is raised by Encoder 1 when an HTL/TTL encoder delivers a speed change that is not plausible: the S120/S150 manual titles the code Encoder 1: Speed change not plausible, the G130/G150 manual the equivalent Encoder 1: Speed difference outside the tolerance range. In both cases the condition is the same — the measured speed change (difference) has exceeded the maximum value in p0492 over several sampling cycles. The change of the averaged speed actual value, where one exists, is monitored in the current controller sampling time. Encoder 1 is involved here in its role as motor encoder; for this case the manual notes that the fault response can be a changeover to encoderless operation. Depending on the drive configuration, the same condition can also be issued as an alarm (A) or with no reaction (N).

Why it appears

  • For an HTL/TTL encoder, the speed change has exceeded the value in p0492 over several sampling cycles (the G130/G150 manual words the same condition as a speed difference outside the tolerance range in p0492).
  • The change to the averaged speed actual value — if applicable — is monitored in the current controller sampling time.

What to check

  1. Check the tachometer feeder cable for interruptions.
  2. Check the grounding of the tachometer shielding.
  3. If required, increase the maximum speed difference per sampling cycle in p0492.

Reading the message value

  • The drive stores the fault value in r0949; interpret it as a decimal number. The manual publishes no decoding — the value is intended only for internal Siemens troubleshooting.

Parameters the manual names

  • p0492 — maximum speed difference per sampling cycle: the threshold monitored by this fault; F31118 trips when the speed change of Encoder 1 exceeds this value over several sampling cycles, and the manual's remedy permits increasing it if required.
  • p0491 — Motor encoder fault response ENCODER: cross-referenced for this fault; it sets the fault response that takes effect when Encoder 1 is used as motor encoder, including the changeover to encoderless operation mentioned for this code.
  • r0949 — fault value: read the decimal fault value of F31118 here; per the manual it serves only internal Siemens troubleshooting.

Acknowledging and restarting

F31118 is acknowledged once the drive has inhibited its pulses (pulse-inhibit acknowledgment); afterwards the drive can be restarted. When the same condition is configured as an alarm (A) or with no reaction (N), the manual specifies neither a reaction nor an acknowledgment.

What differs between the drive families

Straight from the manuals' own fields — F31118 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: NONE Servo: ENCODER (IASC/DCBRK, NONE) Vector: ENCODER (IASC/DCBRK, NONE) Hla: ENCODER (NONE)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 1SINAMICS S120, S150 List Manual · p. 3032
G130, G150Vector: ENCODER (IASC/DCBRK, NONE) Infeed: NONEPULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 1SINAMICS G130, G150 List Manual · p. 1722

The drives this code lives on

F31118 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F31118 mean on a SINAMICS drive?

Encoder 1 — an HTL/TTL encoder used as the motor encoder — has reported a speed change (speed difference) that exceeded the value in p0492 over several sampling cycles.

How do I fix F31118?

Check the tachometer feeder cable for interruptions and check the grounding of the tachometer shielding; if required, increase the maximum speed difference per sampling cycle in p0492.

How is F31118 acknowledged and reset?

The fault is acknowledged once the pulses are inhibited (pulse-inhibit acknowledgment). If the condition is configured as alarm (A) or with no reaction (N), no reaction and no acknowledgment apply.

What is the fault value of F31118 in r0949?

It is interpreted as a decimal number and is intended only for internal Siemens troubleshooting — no decoding is published.