What it means
F31116 is raised by the amplitude/level monitoring of Encoder 1: the amplitude of the rectified encoder signals A and B is no longer inside the tolerance bandwidth. In the variant titled "Amplitude error monitoring track A + B", the monitored quantity also includes the amplitude from the root of A^2 + B^2, and both ends of the band are guarded — the measured level must stay above < 130 mV and below > 955 mV. In the variant titled "Signal level track A or B too low", the stated condition is the signal level of the rectified A and B signals falling below the permissible limit value, with the response threshold < 130 mV (observe the frequency response of the encoder).
Independently of the variant, the nominal level the encoder must deliver is fixed: The nominal signal level of the encoder must lie in the range 375 mV to 600 mV (500 mV -25/+20 %).
Depending on the drive configuration, the same condition can also be output as an alarm or as a message without automatic reaction (A/N).
Why it appears
- The amplitude of the rectified encoder signals A and B — and, in the amplitude-error variant, the amplitude from the root of A^2 + B^2 — of Encoder 1 is not within the tolerance bandwidth.
- In the variant titled "Signal level track A or B too low", the signal level of the rectified A and B signals falls below the permissible limit value.
- Concretely, the measured level is below < 130 mV (observe the frequency response of the encoder) and, on the drives that also monitor the upper threshold, above > 955 mV.
What to check
- Check that the encoder cables and the shielding are routed in compliance with EMC.
- Check the plug connections.
- Replace the encoder or the encoder cable.
- Check the Sensor Module, for example its contacts.
Reading the message value
- The fault value is stored in r0949 and is to be interpreted as hexadecimal yyyyxxxx hex.
- xxxx = signal level, track A (16 bits with sign).
- yyyy = signal level, track B (16 bits with sign).
- The message value is displayed as "A track: %1, B-track: %2", i.e. %1 is the track A level (xxxx) and %2 the track B level (yyyy).
- Reference point: a signal level of 500 mV peak value corresponds to the numerical value 5333 hex = 21299 dec.
- Note: the analog values of the amplitude error are not measured at the same time with the hardware fault output by the Sensor Module.
Parameters the manual names
- r0949 — fault value: read it as hexadecimal yyyyxxxx to see the measured signal levels of track A (xxxx) and track B (yyyy), each 16 bits with sign.
- p0491 — Motor encoder fault response ENCODER: the manual cross-refers to this parameter for F31116; it defines the encoder-specific fault response that takes effect when this monitoring trips.
Acknowledging and restarting
The fault is acknowledged immediately: once the cause has been rectified, the acknowledgment can be issued straight away and the drive restarted. In the alarm (A) and no-reaction (N) variants, the manual specifies no reaction and no acknowledgment.
What differs between the drive families
Straight from the manuals' own fields — F31116 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | Vector: ENCODER (IASC/DCBRK, NONE) Infeed: NONE | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS G130, G150 List Manual · p. 1721 |
| S120, S150 | Infeed: NONE Servo: ENCODER (IASC/DCBRK, NONE) Vector: ENCODER (IASC/DCBRK, NONE) Hla: ENCODER (NONE) | IMMEDIATELY | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS S120, S150 List Manual · p. 3031 |
The drives this code lives on
F31116 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F31116 mean on a SINAMICS converter?
The amplitude/level monitoring for Encoder 1 has tripped: the rectified A and B encoder signals are outside the tolerance band — below < 130 mV, or above > 955 mV where the upper threshold is also monitored.
What signal level should my encoder deliver so F31116 does not trip?
The nominal signal level must lie between 375 mV and 600 mV (500 mV -25/+20 %). In r0949, a level of 500 mV peak value appears as 5333 hex = 21299 dec.
How do I decode the fault value of F31116?
Read r0949 as hexadecimal yyyyxxxx: xxxx is the signal level of track A and yyyy that of track B, each 16 bits with sign. The display shows them as "A track" and "B-track".
How do I fix and reset F31116?
Check the EMC-compliant routing of the encoder cables and shielding, the plug connections, replace the encoder or encoder cable if needed and check the Sensor Module contacts. The fault is then acknowledged immediately.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F31xxx group · SINAMICS manuals · Siemens manuals