Fault · SINAMICS G130, G150, S120, S150

F31101Encoder 1: Zero mark failed

What it means

F31101 is reported as Encoder 1: Zero mark failed: the zero mark monitoring for encoder 1 has tripped because the drive travelled a greater distance without a recognised zero mark than 1.5 times the parameterised zero mark distance. That expected distance is stored in p0425 for a rotary encoder and in p0424 for a linear encoder. Depending on how the drive is configured, the very same condition can also be issued only as an alarm (A) or with no reaction (N) rather than as a fault.

Why it appears

  • The distance covered since POWER ON or since the last detected zero mark exceeded 1.5 times the parameterised zero mark distance, so the zero mark monitoring tripped.
  • The expected clearance between zero marks comes from p0425 (rotary encoder) or p0424 (linear encoder); a value that does not match the encoder actually fitted leads to the same message.

What to check

  1. Lay out and inspect the encoder cables so that their routing complies with EMC requirements.
  2. Check the plug connections of the encoder.
  3. Verify the encoder type — the encoder used must deliver equidistant zero marks.
  4. Adapt p0425, the parameter for the clearance between zero marks, to the encoder actually in use.
  5. If the message is only output above a speed threshold, reduce the filter time in p0438 where necessary.
  6. When bit 1 of p0437 is active, also check p4686.
  7. If the fault persists despite all this, replace the encoder or the encoder cable.

Reading the message value

  • Message value %1: r0949, interpreted as a decimal number, contains the number of increments the drive has counted after POWER ON or since it last detected a zero mark.
  • 4 increments correspond to one encoder pulse, so the value tells you how many increments were counted without a fresh zero mark.

Parameters the manual names

  • p0425 — zero mark distance of the rotary encoder; adapt it to the actual clearance between the zero marks when F31101 occurs.
  • p0424 — zero mark distance of the linear encoder; the monitoring compares against it when encoder 1 is linear, just as against p0425 for a rotary encoder.
  • r0949 — read the fault value here (interpret it as decimal) to see how many increments were counted since POWER ON or the last detected zero mark.
  • p0491 — the motor encoder fault response (ENCODER) that the manual cross-references for this fault; it governs how the drive responds when encoder monitoring trips.
  • p0438 — square-wave encoder filter time; reduce it when the message appears only above a speed threshold.
  • p0437 — extended Sensor Module configuration (SM); if its bit 1 is active, p4686 must be checked for this fault.
  • p4686 — zero mark minimum length; examine this setting whenever bit 1 of p0437 is set.

Acknowledging and restarting

Acknowledging this fault requires pulse inhibit: inhibit the drive pulses, acknowledge the fault, then re-enable the drive and restart. If the cause has not been removed — for example a p0425 setting that does not match the encoder fitted, or a faulty encoder cable — the monitoring trips again as soon as the counted increments exceed the permitted distance once more.

What differs between the drive families

Straight from the manuals' own fields — F31101 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: NONE (OFF1, OFF2) Servo: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2) Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2) Hla: ENCODER (NONE, OFF1, OFF2, OFF3, STOP2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 1SINAMICS S120, S150 List Manual · p. 3026
G130, G150Vector: ENCODER (IASC/DCBRK, NONE, OFF1, OFF2, OFF3, STOP2) Infeed: NONE (OFF1, OFF2)PULSE INHIBITActual position/speed value incorrect or not available (11)Encoder 1SINAMICS G130, G150 List Manual · p. 1716

The drives this code lives on

F31101 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F31101 in SINAMICS mean?

Encoder 1 zero mark monitoring has tripped: the drive counted more increments without a recognised zero mark than 1.5 times the parameterised zero mark distance allows.

Which parameters are relevant for F31101?

p0425 sets the zero mark distance for a rotary encoder and p0424 for a linear one. p0438 (filter time) and p4686 (zero mark minimum length, checked when bit 1 of p0437 is active) also come into play.

How can I read the fault value of F31101?

Open r0949 and interpret the value as a decimal number: it is the increment count since POWER ON or since the last detected zero mark, with 4 increments equal to one encoder pulse.

Why does F31101 appear only at high speed?

The manual addresses exactly this case: if the message is output above a speed threshold, reduce the filter time in p0438 where necessary.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.