What it means
F30950 is raised when an internal software error has occurred in the power unit. The G120XA manual explains the background: an alarm occurred on the power unit that cannot be interpreted by the Control Unit firmware — this can happen when the firmware on the power unit is more recent than the firmware on the Control Unit. The value stored with the fault points to the fault source and is intended only for internal Siemens troubleshooting, so the manual does not decode it for the user.
Why it appears
- An internal software error has occurred in the power unit.
- On the G120XA: an alarm occurred on the power unit that cannot be interpreted by the Control Unit firmware; this can occur if the firmware on the power unit is more recent than the firmware on the Control Unit.
What to check
- If necessary, upgrade the firmware in the power unit to a later version.
- On the G120XA the manual additionally refers to alarm A30999 (Power unit: Unknown alarm) and its firmware measures:
replace the firmware on the power unit by an older firmware version (r0128). Upgrade the firmware on the Control Unit (r0018).
It also notes that, if required, the significance of this new alarm can be read about in a more recent description of the Control Unit. - If the error persists, contact Technical Support.
Reading the message value
- The fault value is stored in r0949 and must be interpreted as a decimal number. It contains information about the fault source and is meant only for internal Siemens troubleshooting; the manual prints no bit or digit decoding for it.
- On the G120XA an alarm value is additionally stored in r2124, likewise interpreted as a decimal number: the alarm number.
Parameters the manual names
- r0949 — fault value: read it as a decimal number; it holds the information about the fault source of this internal software error.
- r2124 — alarm value: on the G120XA it holds the alarm number belonging to this fault, also read as a decimal number.
- r0018 — Control Unit firmware version: check it when you upgrade the Control Unit firmware, the measure the G120XA manual names for this fault.
Acknowledging and restarting
The fault reaction switches the drive off, so the drive coasts down and must be acknowledged before it will start again. Clear the fault by switching the drive's power supply off and on again — but only once the cause has been remedied, i.e. after the firmware work on the power unit (and, on the G120XA, on the Control Unit) or once Technical Support has resolved the error.
What differs between the drive families
Straight from the manuals' own fields — F30950 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G120XA | OFF2 NONE | POWER ON NONE | — | — | SINAMICS G120XA PN converter · p. 1167 |
| S120, S150 | — | POWER ON | Hardware/software error (1) | Power Module | SINAMICS S120, S150 List Manual · p. 3024 |
| G130, G150 | OFF2 | POWER ON | Hardware/software error (1) | Power Module | SINAMICS G130, G150 List Manual · p. 1715 |
| G120 | OFF2 | POWER ON | Hardware/software error (1) | — | SINAMICS G120 · p. 932 |
The drives this code lives on
F30950 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS fault F30950 mean?
The power unit has hit an internal software error. The value in r0949 identifies the fault source, but the manual states it is only for internal Siemens troubleshooting.
How do I clear fault F30950?
Upgrade the firmware in the power unit to a later version if one is available; if the error persists, contact Technical Support. Afterwards acknowledge the fault by switching the drive's power supply off and on again.
Why does F30950 appear after a firmware update on a G120XA?
The power unit raised an alarm that the Control Unit firmware cannot interpret, which can occur when the power unit firmware is more recent than the Control Unit firmware. The manual then suggests an older power unit firmware or an upgrade of the Control Unit firmware.
Which parameters matter for F30950?
r0949 holds the fault value (decimal), on the G120XA r2124 holds the alarm number (decimal), and r0018 shows the Control Unit firmware version.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F30xxx group · SINAMICS manuals · Siemens manuals