SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F30896Power unit DRIVE-CLiQ (CU): Inconsistent component properties

What it means

F30896 tells you that a power unit connected over DRIVE-CLiQ no longer has the properties that were present for this component when the drive booted — the properties have changed in an incompatible fashion, so the drive cannot simply continue operating with the component as it now finds it. The fault value names the component concerned. The condition typically appears after a DRIVE-CLiQ cable or a DRIVE-CLiQ component on the power unit has been replaced. The drive trips and the fault must be acknowledged before it will restart. The manuals that describe this code for the S120/S150 and for the G130/G150 give the same cause and the same remedy, so everything below applies to all of these families.

Why it appears

  • The properties of the DRIVE-CLiQ component (the power unit) named in the fault value have changed in an incompatible fashion with respect to the properties present when the drive booted.
  • One cause given as an example: a DRIVE-CLiQ cable or a DRIVE-CLiQ component has been replaced.

What to check

  1. Read the fault value in r0949 (interpreted as a decimal number) to identify which power unit component the drive considers changed.
  2. Carry out a POWER ON — switch the converter's power supply off and back on.
  3. If a component has been replaced, make sure the new component is of the same component type and, if possible, the same firmware version as the one it replaced.
  4. If a cable has been replaced, use a cable of the same length as, or as close as possible to, the original cable, and ensure compliance with the maximum cable length.

Reading the message value

  • The message value is the component number; the drive prints it as Component number: %1.
  • The drive stores the number of the affected DRIVE-CLiQ power unit component in the fault value r0949 — interpret the value as a decimal number.
  • The manuals give no bit decoding for this value: the whole decimal value is the component number.

Parameters the manual names

  • r0949 — the fault value of the raised message; for F30896 read it here as a decimal number to obtain the component number of the power unit whose properties have changed.

Acknowledging and restarting

The fault may be acknowledged immediately, with no waiting time. Acknowledging alone does not remove the cause: restore a consistent configuration first (same component type and firmware version after a component replacement, a cable of the same or nearly the same length after a cable replacement) and then carry out the POWER ON that the remedy prescribes — switch the converter's power supply off and on again.

What differs between the drive families

Straight from the manuals' own fields — F30896 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: OFF2 (NONE, OFF1) Servo: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Hla: OFF2 (NONE, OFF1, OFF3, STOP2)IMMEDIATELYInternal (DRIVE-CLiQ) communication error (12)Power ModuleSINAMICS S120, S150 List Manual · p. 3022
G130, G150Vector: OFF2 (IASC/DCBRK, NONE, OFF1, OFF3, STOP2) Infeed: OFF2 (NONE, OFF1)IMMEDIATELYInternal (DRIVE-CLiQ) communication error (12)Power ModuleSINAMICS G130, G150 List Manual · p. 1713

The drives this code lives on

F30896 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F30896 mean on a SINAMICS G130, G150, S120 or S150?

The drive has detected that a power unit connected over DRIVE-CLiQ now has properties that are incompatible with those it had when the drive booted. This typically happens after a DRIVE-CLiQ cable or a DRIVE-CLiQ component has been replaced.

How can I see which component triggered F30896?

Read the fault value in r0949 and interpret it as a decimal number — the value is the component number of the power unit component concerned.

How do I clear fault F30896?

Carry out a POWER ON — switch the converter's power supply off and on again — and acknowledge the fault, which can be done immediately. Before restarting, make sure a replaced component is of the same type and firmware version and a replaced cable has the same or nearly the same length as the original.

What cable may I use after a DRIVE-CLiQ cable replacement?

Only a cable whose length is the same as, or as close as possible to, the length of the original cable, while complying with the maximum cable length.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F30xxx group · SINAMICS manuals · Siemens manuals