Fault · SINAMICS G130, G150, S120, S150

F30020Power unit: Configuration not supported

What it means

F30020 is raised when the drive is asked to run the power unit in a configuration that this power unit does not support. The exact reason is coded in r0949, so reading the fault value is the starting point of every diagnosis. The two manual entries differ in one point: for the Motor Module the list of causes also contains fault cause 6.

Why it appears

The low word xxxx of the fault value selects one of these causes:

  • xxxx = 0: autonomous operation was requested although the power unit does not support it.
  • xxxx = 1: the DRIVE-CLiQ timing that was requested is not permissible.
  • xxxx = 2: a PM260 power unit with PS-ASIC version 2 was detected; this pairing is not supported.
  • xxxx = 3: initialization did not run through completely — possibly the Control Unit was pulled out of the Power Module before or while it was powering up.
  • xxxx = 4: this power unit together with this Control Unit or Control Unit Adapter is not a supported combination.
  • xxxx = 5: the higher dynamics of the current controller cannot be used in this configuration.
  • xxxx = 6: the Motor Module, its Control Unit and the firmware version in use may not be combined in this way; the manual lists this cause for the Motor Module only.

What to check

  1. xxxx = 0: if required, deactivate the internal voltage protection that is active (p1231).
  2. xxxx = 1: bring the Control Unit firmware up to date, or adapt the DRIVE-CLiQ topology.
  3. xxxx = 2: swap the power unit for a PM260 with PS-ASIC version 3 or higher.
  4. xxxx = 3 or 4: mount a matching Control Unit or Control Unit Adapter (CUAxx) on the Power Module and then perform a POWER ON of that unit.
  5. xxxx = 5: use a power unit in booksize format, or — on a Double Motor Module — set an identical current controller sampling time for both drive controls (p0115[0]); the higher dynamics then remain usable only on the drive with the longer sampling time. Alternatively, deselect the higher current controller dynamics (p1810.11 = 0), recalculate the controller gains (p0340 = 4) and, if required, optimize the speed controller afterwards.
  6. xxxx = 6: use a Motor Module that suits the setup, or a Control Unit with an approved firmware version.

Reading the message value

  • The drive stores the value in r0949, which is to be interpreted hexadecimal.
  • Format yyyyxxxx hex: the four low digits xxxx hold the fault cause, the four high digits yyyy hold additional information for internal Siemens use.
  • The message text mirrors these two parts as placeholders, fault cause and additional information.
  • The causes xxxx = 0 to xxxx = 6 are decoded in the causes section above.

Parameters the manual names

  • r0949 — read the stored fault value here and separate fault cause from additional information by interpreting it hexadecimal.
  • p1231 — for fault cause 0, use it to deactivate the internal voltage protection if it is active.
  • p0115 — for fault cause 5 on a Double Motor Module, set an identical current controller sampling time in p0115[0] for both drive controls.
  • p1810 — for fault cause 5, setting bit 11 to 0 (p1810.11 = 0) deselects the higher current controller dynamics.
  • p0340 — after deselecting, start the automatic parameter calculation with value 4 so the controller gains are recalculated.

Acknowledging and restarting

First remove the unsupported configuration — the list above names the fix for each fault cause. The drive coasts down when this fault trips; once the cause has been removed, acknowledge the fault and restart the drive. Where the remedy involves the Control Unit or Control Unit Adapter, insert the unit and perform a POWER ON before the restart.

The same on every family

Every manual that describes F30020 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)Power ModuleSINAMICS S120, S150 List Manual · p. 2944
G130, G150OFF2IMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)Power ModuleSINAMICS G130, G150 List Manual · p. 1655

The drives this code lives on

F30020 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F30020 in SINAMICS mean?

The power unit has been asked to run a configuration that it does not support — for example an unsupported pairing of power unit, Control Unit and firmware. The hexadecimal fault value in r0949 tells which of the documented causes applies.

How do I decode the F30020 fault value?

Read r0949 hexadecimal as yyyyxxxx: the low digits xxxx give the fault cause (0 to 6), the high digits yyyy carry additional information used internally by Siemens.

Why does F30020 point to a PM260?

Fault cause 2 means a PM260 power unit with PS-ASIC version 2 was detected, a pairing that is not supported. The remedy is to fit a power unit whose PM260 has PS-ASIC version 3 or higher.

How do I clear and restart after F30020?

Correct the configuration named by the fault cause, then acknowledge the fault and restart. For causes 3 and 4, mount a matching Control Unit or Control Unit Adapter (CUAxx) and perform a POWER ON first.