What it means
F07756 is raised when one of the filter natural frequencies configured for the drive is greater than the Shannon frequency. The drive calculates the Shannon frequency as 0.5 / p0115[0], i.e. from the sampling time for supplementary functions. The fault value in r0949, interpreted as binary, tells you which of the current setpoint filters is the one involved.
Why it appears
- The numerator or denominator natural frequency of one of the current setpoint filters — manipulated variable filter 1, manipulated variable filter 2, the manipulated variable filter or the precontrol filter — is parameterized higher than the Shannon frequency calculated as 0.5 / p0115[0].
What to check
- Read the fault value r0949 interpreted as binary and identify the affected filter from the set bit (bit 0: manipulated variable filter 1, bit 1: manipulated variable filter 2, bit 3: manipulated variable filter, bit 4: precontrol filter).
- Reduce the numerator or denominator natural frequency of the current setpoint filter involved so it no longer exceeds the Shannon frequency 0.5 / p0115[0].
- Alternatively, reduce the controller sampling time (p0115[0]); the Shannon frequency calculated as 0.5 / p0115[0] then rises above the filter natural frequency.
- Or deactivate the filter involved — the activation parameters are p1800 for the manipulated variable filter and p1721 for the precontrol filter.
Reading the message value
- The drive writes the fault value to r0949; interpret it in binary. The set bit names the filter whose natural frequency is too high:
- Bit 0: Manipulated variable filter 1 (p1658, p1660)
- Bit 1: Manipulated variable filter 2 (p1663, p1665)
- Bit 3: Manipulated variable filter (p1800, p1805)
- Bit 4: Precontrol filter (p1721, p1727)
Parameters the manual names
- r0949 — fault value: read it interpreted as binary; the set bit tells you which filter is involved.
- p0115[0] — sampling time for supplementary functions: it defines the Shannon frequency, 0.5 / p0115[0]; reducing this controller sampling time is one of the three remedies.
- p1658 — manipulated variable filter 1 velocity controller denominator natural frequency: reduce it when bit 0 is set.
- p1660 — manipulated variable filter 1 velocity controller numerator natural frequency: reduce it when bit 0 is set.
- p1663 — manipulated variable filter 2 velocity controller denominator natural frequency: reduce it when bit 1 is set.
- p1665 — manipulated variable filter 2 velocity controller numerator natural frequency: reduce it when bit 1 is set.
- p1800 — manipulated variable filter activation: use it to deactivate the filter flagged by bit 3.
- p1805 — manipulated variable filter numerator damping: belongs, together with p1800, to the manipulated variable filter of bit 3.
- p1721 — precontrol filter activation: use it to deactivate the filter flagged by bit 4.
- p1727 — precontrol filter numerator damping: belongs, together with p1721, to the precontrol filter of bit 4.
Acknowledging and restarting
As standard this fault triggers no shutoff of the drive; an automatic response (OFF1, OFF2 or OFF3) can, however, be configured. Acknowledge the fault immediately, and a POWER ON is required before the drive restarts with the corrected setting. So after retuning or deactivating the filter, or after reducing p0115[0], acknowledge F07756 and switch the power supply off and on.
The same on every family
Every manual that describes F07756 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE (OFF1, OFF2, OFF3) | IMMEDIATELY (POWER ON) | Error in the parameterization / configuration / commissioning procedure (18) | Motor | SINAMICS S120, S150 List Manual · p. 2861 |
The drives this code lives on
F07756 is described for S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F07756 mean on SINAMICS?
It means one of the drive's filter natural frequencies is greater than the Shannon frequency, which the drive calculates as 0.5 / p0115[0]. The set bit in r0949 shows which filter is affected.
How do I find out which filter triggered F07756?
Read the fault value r0949 interpreted as binary. Bit 0 means manipulated variable filter 1, bit 1 manipulated variable filter 2, bit 3 the manipulated variable filter and bit 4 the precontrol filter.
Which parameters are behind F07756?
The filter natural frequencies in p1658/p1660, p1663/p1665, p1800/p1805 and p1721/p1727, compared against the Shannon frequency 0.5 / p0115[0]. Which pair matters is shown by the bit in r0949.
How do I clear fault F07756?
Reduce the numerator or denominator natural frequency of the affected filter, reduce the controller sampling time p0115[0], or deactivate the filter involved. Then acknowledge the fault immediately and switch POWER ON.
Codes next to this one