Fault · SINAMICS S120, S150

F07420Drive: Current setpoint filter natural frequency > Shannon frequency

What it means

F07420 is raised when the natural frequency of one of the current setpoint filters is greater than the Shannon frequency. The drive calculates the Shannon frequency as 0.5 / p0115[0], so the limit depends on the sampling time set in p0115[0]. The fault value in r0949 names, bit by bit, which filter is involved; the decoding differs between drive objects — the servo drive objects (SERVO, SERVO_AC, SERVO_I_AC) cover filters 1 to 10, while for A_INF and R_INF only filters 4, 5 and 7 are listed. Filters 5 to 10 belong to the extended current setpoint filter and are marked with r0108.21 in the decoding.

Why it appears

  • One of the filter natural frequencies is greater than the Shannon frequency, which the drive calculates according to the formula 0.5 / p0115[0].

What to check

  1. Read the fault value r0949 in binary and identify from the bit assignment which current setpoint filter is involved; bits 8 ... 15 of the fault value give the data set number (starting from zero).
  2. Reduce the numerator or denominator natural frequency of the current setpoint filter involved (the parameters are assigned to the bits in the lists on this page).
  3. Alternatively reduce the current controller sampling time p0115[0]; since the Shannon frequency is 0.5 / p0115[0], a shorter sampling time raises the limit.
  4. Or switch out the filter involved with p1656.

Reading the message value

The drive writes the fault value into r0949; interpret it binary. A set bit names the filter whose natural frequency is too high.

Drive objects SERVO, SERVO_AC, SERVO_I_AC:

  • Bit 0: Filter 1 (p1658, p1660)
  • Bit 1: Filter 2 (p1663, p1665)
  • Bit 2: Filter 3 (p1668, p1670)
  • Bit 3: Filter 4 (p1673, p1675)
  • Bit 8 ... 15: Data set number (starting from zero)
  • Bit 16: Filter 5 (p5202, p5204) — extended current setpoint filter (r0108.21)
  • Bit 17: Filter 6 (p5207, p5209) — extended current setpoint filter (r0108.21)
  • Bit 18: Filter 7 (p5212, p5214) — extended current setpoint filter (r0108.21)
  • Bit 19: Filter 8 (p5217, p5219) — extended current setpoint filter (r0108.21)
  • Bit 20: Filter 9 (p5222, p5224) — extended current setpoint filter (r0108.21)
  • Bit 21: Filter 10 (p5227, p5229) — extended current setpoint filter (r0108.21)

Drive objects A_INF, R_INF:

  • Bit 3: Filter 4 (p1673, p1675)
  • Bit 16: Filter 5 (p5202, p5204)
  • Bit 18: Filter 7 (p5212, p5214)

Parameters the manual names

The parameter chapter names p1658 to p1675 as the denominator and numerator natural frequencies of the manipulated variable filters of the velocity controller; in this fault they are evaluated as current setpoint filters 1 to 4.

  • r0949 — fault value; read it binary to find the affected filter and the data set number.
  • p0115[0] — sampling time for supplementary functions; it determines the Shannon frequency (0.5 / p0115[0]) and is reduced as one remedy.
  • p1658 / p1660 — denominator and numerator natural frequency of filter 1; lower the value concerned when bit 0 is set.
  • p1663 / p1665 — filter 2, bit 1.
  • p1668 / p1670 — filter 3, bit 2.
  • p1673 / p1675 — filter 4, bit 3.
  • p5202 / p5204 — current setpoint filter 5 (extended current setpoint filter, r0108.21), bit 16.
  • p5207 / p5209 — current setpoint filter 6, bit 17.
  • p5212 / p5214 — current setpoint filter 7, bit 18.
  • p5217 / p5219 — current setpoint filter 8, bit 19.
  • p5222 / p5224 — current setpoint filter 9, bit 20.
  • p5227 / p5229 — current setpoint filter 10, bit 21.
  • p1656 — activation of the manipulated variable filter of the velocity controller; use it to switch out the filter involved.
  • r0108 — bit 21 of this parameter marks the extended current setpoint filter function module to which filters 5 to 10 belong.

Acknowledging and restarting

The drive does not perform an automatic stop for this fault. Correct the filter natural frequency, the sampling time p0115[0] or the filter activation p1656 as described above, then acknowledge the fault — immediate acknowledgement is provided for, and a POWER ON also removes it — and restart the drive. While the parameterization is unchanged, the fault re-appears.

What differs between the drive families

Straight from the manuals' own fields — F07420 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONE (OFF1, OFF2, OFF3)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2809
S120, S150NONE (OFF1, OFF2)IMMEDIATELY (POWER ON)Error in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2809

The drives this code lives on

F07420 is described for S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F07420 mean?

It is raised when the natural frequency of one of the current setpoint filters is greater than the Shannon frequency, which the drive calculates as 0.5 / p0115[0]. The fault value r0949, read in binary, names the filter concerned.

How do I fix fault F07420?

Reduce the numerator or denominator natural frequency of the filter named by r0949, reduce the current controller sampling time p0115[0], or switch the filter out with p1656. Then acknowledge the fault and restart the drive.

Which parameters are checked by F07420?

Filters 1 to 4 via p1658/p1660, p1663/p1665, p1668/p1670 and p1673/p1675, extended filters 5 to 10 via p5202/p5204 up to p5227/p5229, plus the sampling time p0115[0] and the filter activation p1656.

Why does F07420 only name filters 4, 5 and 7 on my drive?

For the A_INF and R_INF drive objects the fault value decoding covers only bit 3 (filter 4), bit 16 (filter 5) and bit 18 (filter 7). The full decoding with filters 1 to 10 applies to the SERVO, SERVO_AC and SERVO_I_AC drive objects.

Codes next to this one