Fault · SINAMICS G130, G150, S120, S150

F05119Bypass contactor simultaneity monitoring time exceeded

What it means

F05119 means that the simultaneity monitoring of the bypass contactors has responded. The monitoring runs because a feedback signal for the bypass contactor is interconnected and the simultaneity monitoring (p0255[5, 7]) is activated. After a contactor of the parallel connection was opened or closed, the set monitoring time elapsed while not all of the contactors had assumed the same state.

The same condition can also be signalled as an alarm (A); as an alarm it causes no automatic reaction and requires no acknowledgement.

Why it appears

  • After opening or closing a contactor of the parallel connection, the monitoring time elapsed and not all of the contactors had assumed the same state.
  • The monitoring is active only when a feedback signal for the bypass contactor is interconnected and the simultaneity monitoring (p0255[5, 7]) is activated.

What to check

  1. Check the monitoring time setting in p0255[5, 7].
  2. Check the wiring and the control of the contactor.
  3. If required, replace the contactor.

Reading the message value

The drive writes the fault value into r0949; interpret it binary as yyyyxxxx hex, where yyyy is the supplementary information and xxxx is the fault cause. The message value itself contains the fault cause and the additional information.

  • Fault cause (xxxx): Bit 0 = 1: simultaneity error when closing the contactors; Bit 1 = 1: simultaneity error when opening the contactors.
  • Supplementary information (yyyy): Bit 0 = 1: PDS0 contactor is closed; Bit 1 = 1: PDS1 contactor is closed; Bit 2 = 1: PDS2 contactor is closed; Bit 3 = 1: PDS3 contactor is closed; Bit 4 = 1: PDS4 contactor is closed; Bit 5 = 1: PDS5 contactor is closed; Bit 6 = 1: PDS6 contactor is closed; Bit 7 = 1: PDS7 contactor is closed.

PDS means Power unit Data Set.

Parameters the manual names

  • p0255 (Power unit contactor monitoring time, PU cont t_mon): holds the monitoring time of the contactor simultaneity monitoring in indices [5, 7]; check the set time here for this fault.
  • r0949 (Fault value): read it binary as yyyyxxxx hex to determine whether the simultaneity error occurred when closing or opening and which PDS contactors are closed.

Acknowledging and restarting

The fault switches the drive off (OFF2) — alternatively OFF1 or no reaction can be configured — and the drive must be acknowledged before it will restart. Once the cause has been remedied, acknowledge the fault immediately (POWER ON). If the condition is configured as an alarm (A), there is no automatic reaction and no acknowledgement is required.

What differs between the drive families

Straight from the manuals' own fields — F05119 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150OFF2 (NONE, OFF1)Infeed faulted (13)Power ModuleSINAMICS S120, S150 List Manual · p. 2753
G130, G150OFF2 (NONE, OFF1)IMMEDIATELY (POWER ON)Infeed faulted (13)Power ModuleSINAMICS G130, G150 List Manual · p. 1526

The drives this code lives on

F05119 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F05119 mean?

The bypass contactor simultaneity monitoring time has been exceeded: after opening or closing a contactor of the parallel connection, not all contactors assumed the same state within the monitoring time.

Which parameter belongs to F05119?

p0255 — Power unit contactor monitoring time. The bypass contactor simultaneity monitoring uses indices [5, 7], and its setting should be checked first.

How do I fix and reset F05119?

Check the monitoring time in p0255[5, 7], check the wiring and control of the contactor, and replace the contactor if required. Then acknowledge the fault immediately (POWER ON) before restarting.

How is the fault value of F05119 decoded?

In r0949, interpret the value binary as yyyyxxxx hex: the low nibble shows a simultaneity error on closing (Bit 0) or opening (Bit 1), and the high nibble shows which PDS0–PDS7 contactors are closed.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.