SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Fault · SINAMICS G130, G150, S120, S150

F01800DRIVE-CLiQ: Hardware/configuration error

What it means

F01800 is raised when the drive detects a fault on its DRIVE-CLiQ wiring or configuration. The drive writes a fault value to r0949 — to be read as a decimal number — which distinguishes the individual cases: a DRIVE-CLiQ socket that has not entered cyclic operation (100 ... 107), a lost connection (10), repeated faults while detecting the connection (11), or a node whose ID exchange mechanism fails (12). Depending on the drive configuration, the same condition can also be signaled as an alarm.

Why it appears

  • Values 100 ... 107: the DRIVE-CLiQ socket concerned (X100 ... X107) never entered cyclic operation — either the bus structure is built incorrectly or the configuration demands a bus timing that cannot be achieved.
  • Value 10: the DRIVE-CLiQ connection dropped out, typically because a cable was withdrawn from the Control Unit or because of a short-circuit on a motor equipped with DRIVE-CLiQ.
  • Value 11: while the drive was detecting its DRIVE-CLiQ connections, faults kept recurring.
  • Value 12: although a connection was detected, the node ID exchange mechanism does not work — the component involved is probably defective.

What to check

  1. Read the fault value in r0949 (interpret it as a decimal number) to determine which of the cases below applies.
  2. For values 100 ... 107: ensure that all DRIVE-CLiQ components carry the same firmware versions, and avoid longer topologies when the current controller clock cycle (sampling time) is short.
  3. For value 10: check the DRIVE-CLiQ cables at the Control Unit, remove any short-circuit on motors with DRIVE-CLiQ, then carry out a POWER ON.
  4. For value 11: check the electrical cabinet design and the cable routing for EMC compliance.
  5. For value 12: replace the component involved.

Reading the message value

  • 100 ... 107 — communication via DRIVE-CLiQ socket X100 ... X107 has not been switched to cyclic operation; the cause may be an incorrect structure or a configuration that results in an impossible bus timing.
  • 10 — loss of the DRIVE-CLiQ connection, for example because the DRIVE-CLiQ cable was withdrawn from the Control Unit or as a result of a short-circuit for motors with DRIVE-CLiQ. This fault can only be acknowledged in cyclic communication.
  • 11 — repeated faults when detecting the connection; this fault can also only be acknowledged in cyclic communication.
  • 12 — a connection was detected, but the node ID exchange mechanism does not function; the component is probably defective. This fault likewise only clears in cyclic communication.

Parameters the manual names

  • r0949 — displays the fault value of F01800; read it as a decimal number to identify the failed DRIVE-CLiQ socket (100 ... 107 = X100 ... X107), a lost connection (10), recurring faults during connection detection (11) or a failed node ID exchange (12).

Acknowledging and restarting

Acknowledge the fault immediately; the specified acknowledgement is POWER ON, i.e. switch the drive off and on again. For fault values 10, 11 and 12 the drive only accepts the acknowledgement in cyclic communication, so the DRIVE-CLiQ connection must be working again first — the remedy for a lost connection (fault value 10) therefore ends with a POWER ON. If the drive is configured to signal this condition as an alarm, no acknowledgement is required.

What differs between the drive families

Straight from the manuals' own fields — F01800 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150Infeed: NONE (OFF1, OFF2) Servo: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2) Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2) Hla: NONE (OFF1, OFF2, OFF3, STOP2)IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS S120, S150 List Manual · p. 2708
G130, G150Vector: NONE (IASC/DCBRK, OFF1, OFF2, OFF3, STOP2) Infeed: NONE (OFF1, OFF2)IMMEDIATELY (POWER ON)Internal (DRIVE-CLiQ) communication error (12)NoneSINAMICS G130, G150 List Manual · p. 1487

The drives this code lives on

F01800 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01800 mean on a SINAMICS drive?

It signals a DRIVE-CLiQ hardware or configuration fault. The fault value in r0949, read as a decimal number, shows whether a socket, the cable connection, the connection detection or the node ID exchange is affected.

How do I clear F01800 with fault value 10?

Check the DRIVE-CLiQ cables at the Control Unit, remove any short-circuit on motors with DRIVE-CLiQ, and then carry out a POWER ON. The fault can only be acknowledged once cyclic communication is running again.

Why does F01800 show a fault value between 100 and 107?

The number identifies the DRIVE-CLiQ socket X100 ... X107 whose communication has not been switched to cyclic operation, usually because of an incorrect structure or an impossible bus timing. Match the firmware versions of the DRIVE-CLiQ components and avoid long topologies with short current controller clock cycles.

Why can F01800 not be acknowledged?

For fault values 10, 11 and 12 the fault can only be acknowledged in cyclic communication, so the DRIVE-CLiQ connection must first be restored. With value 12 the component involved is probably defective and has to be replaced.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals