Fault · SINAMICS G120, G130, G150, S120, S150

F01665SI P1 (CU): System is defective

What it means

The SI processor 1 (P1) in the Control Unit (CU) reports that a system defect was detected — either before the last time the system booted or in the actual boot. The system might also have rebooted itself (reset). Which of these situations the drive has caught is shown by the fault value in r0949, interpreted hexadecimal: it distinguishes a defect from an earlier boot, a fault in the current booting/operation, a mismatch around the "STO via terminals at the Power Module" function (STO — Safe Torque Off) on a Power Module with terminals STO_A/STO_B, and a mismatch between the SI Motion monitoring clock cycles of the Control Unit and the Motor Module.

Why it appears

  • A system defect was detected before the last boot or in the actual one, and the system might have been rebooted (reset).
  • For a Power Module with "STO via terminals at the Power Module" (terminals STO_A/STO_B): the terminals are active (DIP switch to "ON") while the function has not been enabled — p9601.7 = p9801.7 = 0. The manuals describe this case for the G120.
  • The fault lies in the actual booting or in operation.
  • The SI Motion monitoring clock cycles of the Control Unit (p9500) and of the Motor Module (p9300) are, under certain circumstances, not the same; Safety message C01711/C30711 is displayed in addition.

What to check

  1. Read the fault value in r0949 and interpret it hexadecimal — the remedy depends on it.
  2. Carry out a POWER ON (switch-off/switch-on); this is the first remedy for every fault value.
  3. For fault value 40 hex: deactivate the terminals STO_A/STO_B on the Power Module (set both DIP switches to "OFF") or enable the "STO via terminals at the Power Module" function.
  4. For fault value 200000 hex, 400000 hex or 8000yy hex (yy any): ensure that the Control Unit is connected to the Power Module; for the G120, the remedy adds to deselect the "STO via terminals at the Power Module" function.
  5. For fault value 800004 hex: check that parameters p9500/p9300 are the same.
  6. Otherwise, upgrade the firmware to a later version and contact Technical Support.

Reading the message value

The drive stores the fault value in r0949; interpret the value hexadecimal.

  • 40 hex — a Power Module with "STO via terminals at the Power Module" (STO_A/STO_B) has its terminals active (DIP switch to "ON") although the function is not enabled (p9601.7 = p9801.7 = 0).
  • 200000 hex, 400000 hex, 8000yy hex (yy any) — fault in the actual booting/operation.
  • 800004 hex — parameters p9500/p9300 are, under certain circumstances, not the same; Safety message C01711/C30711 is displayed in addition.
  • Additional values — defect before the last time that the system booted.

Parameters the manual names

  • r0949 (fault value): read here and interpret hexadecimal — the value tells which situation the drive is reporting and which remedy applies.
  • p9601 — SI enable functions integrated in the drive (processor 1): carries the enable of the "STO via terminals at the Power Module" function; with fault value 40 hex, bit 7 is 0 while the STO_A/STO_B terminals are active.
  • p9801 — SI enable functions integrated in the drive (processor 2): carries the same enable on the second processor; with fault value 40 hex, bit 7 is 0 here as well.
  • p9500 — SI Motion monitoring clock cycle (Control Unit): with fault value 800004 hex, check here that the clock cycle matches p9300.
  • p9300 — SI Motion monitoring clock cycle (Motor Module): the value compared against p9500 when fault value 800004 hex appears.

Acknowledging and restarting

The drive coasts down (OFF2) and the fault must be acknowledged immediately before it will start again. Because the defect may already date from before the last boot, the first remedy is a POWER ON — switch the converter off and on again. If the fault then comes back, work through the value-specific checks and finally upgrade the firmware to a later version and contact Technical Support.

What differs between the drive families

Straight from the manuals' own fields — F01665 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G120OFF2IMMEDIATELYHardware/software error (1)SINAMICS G120 · p. 846
S120, S150OFF2IMMEDIATELYHardware/software error (1)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2647
G130, G150OFF2IMMEDIATELYHardware/software error (1)Control Unit (CU)SINAMICS G130, G150 List Manual · p. 1446

The drives this code lives on

F01665 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does fault F01665 SI P1 (CU): System is defective mean?

The SI processor 1 in the Control Unit has detected a system defect, either before the last boot or in the actual one, and the system might have been rebooted (reset). The fault value in r0949, read hexadecimal, shows which situation applies.

How do I clear fault F01665?

Acknowledge immediately and carry out a POWER ON (switch-off/switch-on). Then, depending on the fault value, deactivate or enable the STO terminals on the Power Module, make sure the Control Unit is connected to the Power Module, or match p9500 with p9300; if the fault persists, upgrade the firmware or contact Technical Support.

What does fault value 800004 hex in F01665 mean?

The SI Motion monitoring clock cycle parameters p9500 (Control Unit) and p9300 (Motor Module) are, under certain circumstances, not the same, and Safety message C01711/C30711 is displayed as well. Check that p9500 and p9300 match.

Why does F01665 come with fault value 40 hex on a Power Module with STO terminals?