Fault · SINAMICS G120, G120XA, G130, G150, S120, S150

F01112CU: Power unit not permissible

What it means

F01112 reports that the power unit connected to the Control Unit (CU) is not permissible for this combination — the CU cannot be used together with this power unit. The manuals describe the fault for SINAMICS G120, G120XA, G130, G150, S120 and S150; the concrete reason is stored as a decimal value in r0949, and the list of possible values differs slightly between the families (see below).

Why it appears

  • The power unit connected to this Control Unit is not a permissible combination — the CU does not support it for this use.
  • Which case applies is stored in r0949: an unsupported power unit type (e.g. PM240 on G130/G150/S120/S150, e.g. PM340 on G120/G120XA), a DC/AC power unit connected to a CU310, or an S120M power unit used for vector control — the last two are listed for G130, G150, S120 and S150 only.

What to check

  1. Read the fault value in r0949 and interpret it as a decimal number to identify which combination was rejected.
  2. Replace the non-permissible power unit with a component that is permissible.

Reading the message value

  • The drive writes the reason for F01112 into r0949; interpret the value as a decimal number.
  • 1 — Power unit is not supported (e.g. PM240 on G130, G150, S120 and S150; e.g. PM340 on G120 and G120XA).
  • 2 — DC/AC power unit connected to CU310 not permissible (listed for G130, G150, S120 and S150).
  • 3 — Power unit (S120M) not permitted for vector control (listed for G130, G150, S120 and S150).

Parameters the manual names

  • r0949 — fault value: read it as a decimal number for this fault; the value (1, 2 or 3) identifies why the connected power unit was rejected.

Acknowledging and restarting

The drive triggers no automatic shutdown for this fault. Once the non-permissible power unit has been replaced by a permissible component, acknowledge the fault immediately; the acknowledgment clears the message.

What differs between the drive families

Straight from the manuals' own fields — F01112 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1391
S120, S150NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2579
G120NONEIMMEDIATELYError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 831
G120XANONEIMMEDIATELYSINAMICS G120XA PN converter · p. 1108

The drives this code lives on

F01112 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault F01112 mean?

The Control Unit has detected that the connected power unit cannot be used together with it — the combination is not permissible. The fault is described for SINAMICS G120, G120XA, G130, G150, S120 and S150.

How do I find the reason for F01112?

Read the fault value in r0949 as a decimal number. Value 1 means the power unit type is not supported (e.g. PM240 on G130/G150/S120/S150, e.g. PM340 on G120/G120XA), value 2 that a DC/AC power unit is connected to a CU310, and value 3 that an S120M power unit is not permitted for vector control; values 2 and 3 are printed for G130, G150, S120 and S150 only.

How do I clear F01112?

Replace the non-permissible power unit with a permissible component and then acknowledge the fault immediately. The drive performs no automatic shutdown for this fault.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals