What it means
F01111 is raised by the Control Unit (CU) when power units of different drive types are operated on one and the same Control Unit — a mixed operation of drive units that the manuals call illegal. All manuals that describe this fault state the same causes and the same remedy, so the explanation below holds for every converter family on which the code appears.
Why it appears
- Drive units of different types are operated together on one Control Unit.
- Illegal combination named in the manuals: SINAMICS S together with SINAMICS G.
- Illegal combination named in the manuals: SINAMICS S together with SINAMICS S Value or Combi.
What to check
- Read the fault value in r0949, interpreting it as a decimal number: it gives the number of the first drive object with a different power unit type, i.e. the point where the mixing begins.
- Establish which power unit types are operated on this Control Unit and where one of the illegal combinations occurs (SINAMICS S together with SINAMICS G, or SINAMICS S together with SINAMICS S Value or Combi).
- Change the configuration so that only power units of one particular drive type are operated with the Control Unit — this is the remedy the manuals give.
- Acknowledge the fault immediately once the mixed operation has been removed.
Reading the message value
- The drive outputs the fault value as message value %1; the same value can be read in r0949.
- Read the value as a decimal number, not as a bit pattern.
- Meaning: number of the first drive object with a different power unit type.
Parameters the manual names
- r0949 (fault value): read here, interpreted as a decimal number, to identify the number of the first drive object whose power unit type differs from the others.
Acknowledging and restarting
First remove the illegal mix — only power units of one particular drive type may be operated with one Control Unit — and then acknowledge the fault immediately; no further reset action is described for this code.
The same on every family
Every manual that describes F01111 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| G130, G150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1391 |
| S120, S150 | NONE | IMMEDIATELY | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2579 |
The drives this code lives on
F01111 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault F01111 mean in SINAMICS?
The Control Unit has detected power units of different drive types operated together on one Control Unit. The illegal combinations are SINAMICS S together with SINAMICS G, and SINAMICS S together with SINAMICS S Value or Combi.
How do I find the drive object that triggers F01111?
Read the fault value in r0949 and interpret it as a decimal number. It is the number of the first drive object with a different power unit type.
How do I clear fault F01111?
Operate only power units of one particular drive type on the Control Unit, then acknowledge the fault immediately.
Does F01111 shut the drive down?
No automatic drive response is triggered by this fault; it reports a configuration error that must be corrected and acknowledged immediately.
Codes next to this one
Source
Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.
All SINAMICS codes: fault and alarm codes · the F01xxx group · SINAMICS manuals · Siemens manuals