Safety message · SINAMICS G130, G150, S120, S150

C01797SI Motion P1 (CU): Axis not safely referenced

What it means

C01797 is a Safety Integrated (SI) message of the SI Motion P1 monitoring on the Control Unit (CU): the axis is not safely referenced. The drive raises it when the standstill position that was saved before switching off does not match the actual position determined at switch-on. The drive does not perform a stop in response to this message; the condition must be resolved by re-establishing a safety-relevant reference for the axis.

Why it appears

  • The standstill position saved before the drive was switched off does not match the actual position determined at switch-on.

What to check

  1. Determine whether safe automatic referencing of the axis is possible.
  2. If safe automatic referencing is not possible, the user must issue a user agreement for the new position using the softkey; this position is then designated as safety-relevant.

Reading the message value

The drive stores the message value in r9749; interpret it as a decimal value:

  • 1: Axis not safely referenced.
  • 2: User agreement missing.

Parameters the manual names

  • r9749 (SI message value / SI msg_value) — read the message value of this message here as a decimal number: 1 means the axis is not safely referenced, 2 means the user agreement is missing.

Acknowledging and restarting

Acknowledge the message immediately with a POWER ON: switch the drive off and on again. Before restarting, make sure the safe reference has been restored — either by safe automatic referencing or by the user agreement issued via the softkey, as described above.

The same on every family

Every manual that describes C01797 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS S120, S150 List Manual · p. 2707
G130, G150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS G130, G150 List Manual · p. 1486

The drives this code lives on

C01797 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault C01797 mean?

It is an SI Motion P1 safety message from the Control Unit: the standstill position saved before switching off does not match the actual position determined at switch-on, so the axis is not safely referenced.

How do I clear C01797?

If safe automatic referencing is not possible, the user must issue a user agreement for the new position using the softkey; that position is then designated as safety-relevant. The message is then acknowledged by switching the drive off and on again (POWER ON).

What do the message values 1 and 2 in r9749 mean for C01797?

Read r9749 as a decimal value: 1 means the axis is not safely referenced, and 2 means the user agreement is missing.

Does C01797 stop the drive?

No — the drive does not execute a stop reaction for this message; it reports the missing safe reference. The message still has to be acknowledged immediately with a POWER ON.