Safety message · SINAMICS G130, G150, S120, S150

C01730SI Motion P1 (CU): Reference block for dynamic Safely-Limited Speed invalid

What it means

C01730 comes from the Safety Integrated (SI) monitoring of SI Motion P1 in the Control Unit (CU). The higher-level control transfers a reference block via PROFIsafe, and this block is used to generate the referred velocity limit value for the dynamic Safely-Limited Speed (SLS) function from the reference quantity "Velocity limit value SLS1" (p9531[0]). The safety monitoring channel has identified that the transferred block is invalid, and the drive is stopped as a result of the stop response configured in p9563[0]. The manual's abbreviations: SI = Safety Integrated, SLS = Safely-Limited Speed, SG = Safely reduced speed. Other messages of the same SI Motion P1 group, e.g. C01714 (Safely Limited Speed exceeded) or C01710 (STOP E initiated), are described on their own pages.

Why it appears

  • The reference block transferred via PROFIsafe is negative. Such a block serves to generate the referred velocity limit value from the reference quantity "Velocity limit value SLS1" (p9531[0]). Both manuals describe this cause identically for the listed drive objects, so there is only this one cause.

What to check

  1. Read the message value in r9749 and interpret it decimal — it identifies the condition as "requested, invalid reference block".
  2. In the PROFIsafe telegram, input data S_SLS_LIMIT_IST must be corrected. The block currently transferred is negative, so the value sent in the PROFIsafe telegram has to be corrected.

Reading the message value

  • The drive stores the message value in r9749; the manual specifies to interpret it decimal.
  • For C01730 the value means: requested, invalid reference block. The manual gives no further bit decoding for this message.

Parameters the manual names

  • p9531[0] — "Velocity limit value SLS1": the SI Motion SLS (SG) limit values of the Control Unit; this is the reference quantity from which the referred velocity limit value is generated.
  • p9563[0] — the SI Motion SLS (SG)-specific stop response of the Control Unit; with the response configured here the drive is stopped when this message occurs.
  • r9749 — the SI message value; read it (interpret decimal) to confirm that an invalid reference block was requested.

Acknowledging and restarting

Correct input data S_SLS_LIMIT_IST in the PROFIsafe telegram first. The manual then explicitly allows acknowledging this message without a POWER ON: it names safe acknowledgment via PROFIsafe as the way to do this.

The same on every family

Every manual that describes C01730 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS S120, S150 List Manual · p. 2696
G130, G150NONEIMMEDIATELY (POWER ON)Safety monitoring channel has identified an error (10)NoneSINAMICS G130, G150 List Manual · p. 1475

The drives this code lives on

C01730 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS fault C01730 mean?

The SI Motion P1 safety monitoring channel in the Control Unit has received a negative reference block via PROFIsafe. This block is used to generate the referred velocity limit value for the dynamic Safely-Limited Speed function from "Velocity limit value SLS1" (p9531[0]).

How do I fix and clear C01730?

Correct input data S_SLS_LIMIT_IST in the PROFIsafe telegram. Afterwards the message can be acknowledged without a POWER ON using safe acknowledgment via PROFIsafe.

What is stored in the message value of C01730?

The value is in r9749 and is to be interpreted decimal; it stands for "requested, invalid reference block".

Why is the drive stopped when C01730 appears?

The drive is stopped as a result of the stop response configured in p9563[0], the SI Motion SLS (SG)-specific stop response of the Control Unit.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.