What it means
A33920 is raised by the Sensor Module Encoder 3 when the motor temperature sensor connected to it cannot be evaluated: the measured resistance lies outside the range the module expects for the selected sensor type. The manuals print the condition as an alarm; depending on the drive's configuration the same condition can also be output as a fault or as a message without a response. On S120 and S150 the manual titles it Encoder 3: Temperature sensor fault (motor)
. The condition does not make the drive trip — it only reports the sensor problem.
Why it appears
- An error occurred while the module was evaluating the temperature sensor. Two fault causes are distinguished: a wire breakage or a sensor that is not connected, and a measured resistance that is too low for the selected sensor type (PTC, KTY or PT1000).
- Which of the two applies is coded in the message value; the manuals also print additional values that are only for internal Siemens troubleshooting.
What to check
- Check that the encoder cable is the correct type and is correctly connected.
- Check the temperature sensor selection in p0600 to p0603.
- If the cable and the sensor selection are in order, replace the Sensor Module — the manual names a hardware defect or incorrect calibration data as the remaining reasons.
Reading the message value
- The message value carries two items: the fault cause (%1) and the channel number (%2).
- In r0949 or r2124 the information is coded as 0000yyxx hex: yy = channel number, xx = error cause.
- Error cause 1 (= 01 hex): wire breakage or sensor not connected — KTY: R > 1630 Ohm, PT1000: R > 1720 Ohm.
- Error cause 2 (= 02 hex): measured resistance too low — PTC: R < 20 Ohm, KTY: R < 50 Ohm, PT1000: R < 603 Ohm.
- Additional values: only for internal Siemens troubleshooting.
Parameters the manual names
- r0949 (fault value): holds the coded message value when the condition is stored as a fault — fault cause and channel number in the 0000yyxx hex pattern described above.
- r2124 (alarm value): the same readout while the condition is active as alarm A33920.
- p0600 (motor temperature sensor for monitoring): check that the sensor type actually connected to Encoder 3 is the one selected here.
- p0603 (CI: motor temperature signal source): check which signal source is interconnected as the motor temperature for this encoder.
Acknowledging and restarting
As an alarm, A33920 requires no acknowledgement: it is present only while the sensor signal is outside the permissible range and disappears once the signal is back to normal. The drive is not switched off by the condition itself. Where the configuration issues the same condition as a fault, it can be acknowledged right away — without a power-up cycle or waiting period — and the drive can run again as soon as the cause (cable, sensor selection or Sensor Module) has been remedied.
The same on every family
Every manual that describes A33920 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Sensor Module Encoder 3 | SINAMICS S120, S150 List Manual · p. 3180 |
| G130, G150 | NONE | NONE | External measured value / signal state outside the permissible range (16) | Sensor Module Encoder 3 | SINAMICS G130, G150 List Manual · p. 1850 |
The drives this code lives on
A33920 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does fault cause 1 (01 hex) of A33920 mean?
It means wire breakage or that the sensor is not connected. The resistance measured is above the upper limit for the sensor type — above 1630 Ohm for KTY or above 1720 Ohm for PT1000.
Which resistances trigger fault cause 2 of A33920?
A resistance below the minimum for the selected sensor type: below 20 Ohm for PTC, below 50 Ohm for KTY and below 603 Ohm for PT1000.
How do I see which channel is affected?
Read the message value in r0949 or r2124. It is coded 0000yyxx hex: yy gives the channel number and xx the error cause.
Does A33920 stop the drive or need a special reset?
No. The condition does not trip the drive; as an alarm it needs no acknowledgement and clears itself once the signal is back in range, and as a fault it can be acknowledged right away.