What it means
A33443 is raised when the unipolar signal level on track C/D of Encoder 3 leaves the permissible tolerance — either on CP/CN or on DP/DN. The unipolar nominal signal level of the encoder must lie in the range 2500 mV +/- 500 mV; the drive responds once the level falls below 1700 mV or rises above 3300 mV. The level is only evaluated when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1). Depending on the drive configuration, the same condition can also be issued as fault F33443 or as a message without reaction (N33443).
Why it appears
- The unipolar level (CP/CN or DP/DN) for Encoder 3 is outside the permissible tolerance: the nominal level must lie in the range 2500 mV +/- 500 mV, and the drive responds below 1700 mV or above 3300 mV.
What to check
- Check that the encoder cables and shielding are routed in compliance with EMC.
- Check the plug connections and contacts of the encoder cable.
- Check whether the C/D tracks are connected correctly — have the signal cables CP and CN or DP and DN been interchanged?
- Replace the encoder cable.
Reading the message value
- The drive writes the alarm value to r2124; interpret it in binary.
- Bit 0 = 1: either CP or CN is outside the tolerance.
- Bit 16 = 1: either DP or DN is outside the tolerance.
Parameters the manual names
- r2124 — read the alarm value here in binary to see whether CP/CN (bit 0) or DP/DN (bit 16) is outside the tolerance.
- r0459 — Sensor Module properties extended: bit 31 must read 1 (Sensor Module properties available); the C/D signal level is only evaluated when it is set.
- p0437 — Sensor Module configuration extended: bit 31 switches monitoring on; the C/D signal level is only evaluated while monitoring is active.
Acknowledging and restarting
As an alarm, A33443 requires no acknowledgement. If the drive is configured to issue the same condition as fault F33443, the drive still takes no automatic reaction, but the fault must be acknowledged IMMEDIATELY.
The same on every family
Every manual that describes A33443 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 3 | SINAMICS S120, S150 List Manual · p. 3160 |
| G130, G150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 3 | SINAMICS G130, G150 List Manual · p. 1832 |
The drives this code lives on
A33443 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A33443 mean?
The unipolar signal level on track C/D of Encoder 3 — on CP/CN or on DP/DN — is outside the permissible tolerance. The nominal level is 2500 mV +/- 500 mV; the drive reacts below 1700 mV or above 3300 mV.
How can I see whether CP/CN or DP/DN is affected?
Read alarm value r2124 and interpret it in binary: bit 0 = 1 means either CP or CN is outside the tolerance, bit 16 = 1 means either DP or DN.
Does A33443 stop the drive, and how is it acknowledged?
No — as an alarm it requires no acknowledgement. Even if the drive is configured to issue the same condition as fault F33443, it takes no automatic reaction; the fault must then be acknowledged IMMEDIATELY.
Why is the C/D signal level not being evaluated at all?
The level is only evaluated when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1).