SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G130, G150, S120, S150

A31443Encoder 1: Signal level track C/D outside tolerance (alarm)

What it means

A31443 reports that the unipolar signal level of encoder 1 is outside the permissible tolerance: the unipolar level (CP/CN or DP/DN) has left the allowed band. The manuals print the code as Encoder 1: Signal level track C/D outside tolerance (alarm) and also as Encoder 1: Unipolar CD signal level outside specification — different wording, same condition. The unipolar nominal signal level of the encoder must lie in the range 2500 mV +/- 500 mV; the drive responds when the level falls below 1700 mV or rises above 3300 mV. Depending on how the drive is configured, the same condition can also be issued as a fault (F) or as a message without reaction (N). The signal level is only evaluated when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1).

Why it appears

  • The unipolar level (CP/CN or DP/DN) for encoder 1 is outside the permissible tolerance: the nominal signal level must lie in the range 2500 mV +/- 500 mV, and the response thresholds are below 1700 mV and above 3300 mV.

What to check

  1. Check that the encoder cables and shielding are routed in compliance with EMC.
  2. Check the plug connections and contacts of the encoder cable.
  3. Check that the C/D tracks are connected correctly — have the signal cables CP and CN or DP and DN been interchanged?
  4. Replace the encoder cable.

Reading the message value

The message value is the alarm value stored in r2124, interpreted binary ("Fault cause: %1 bin").

  • Bit 0 = 1: either CP or CN outside the tolerance.
  • Bit 16 = 1: either DP or DN outside the tolerance.

Parameters the manual names

  • r2124 — holds the alarm value for this message; read it as a binary pattern to see which pair is affected (bit 0: CP/CN, bit 16: DP/DN).
  • r0459 — Sensor Module properties extended; the signal level is only evaluated when r0459.31 = 1 (Sensor Module properties available).
  • p0437 — Sensor Module configuration extended; monitoring of the signal level is only active when p0437.31 = 1.
  • p0491 — motor encoder fault response ENCODER; sets how the drive reacts if the same condition is raised as a fault.

Acknowledging and restarting

As an alarm, A31443 triggers no automatic response and needs no acknowledgement: it clears itself once the unipolar level is back inside the tolerance. If the drive is configured to raise the same condition as a fault (response set in p0491), the fault must be acknowledged immediately before the drive can be restarted.

The same on every family

Every manual that describes A31443 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 1SINAMICS S120, S150 List Manual · p. 3056
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 1SINAMICS G130, G150 List Manual · p. 1741

The drives this code lives on

A31443 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A31443 on a SINAMICS drive mean?

It reports that the unipolar signal level of encoder 1 — the CP/CN or DP/DN level of the C/D tracks — is outside the permissible tolerance. The nominal level is 2500 mV +/- 500 mV; the drive responds below 1700 mV or above 3300 mV.

How can I see whether the CP/CN level or the DP/DN level is affected?

Read the alarm value in r2124 as a binary pattern. Bit 0 set means either CP or CN is outside the tolerance; bit 16 set means either DP or DN is outside the tolerance.

Does A31443 stop the drive?

No. As an alarm it triggers no automatic reaction and needs no acknowledgement; it clears itself when the signal level returns to the tolerance. If the condition is configured as a fault (p0491), it must be acknowledged immediately before restart.

Why is the encoder signal level not being monitored at all?

The signal level is only evaluated when the Sensor Module properties are available (r0459.31 = 1) and monitoring is active (p0437.31 = 1). If either condition is not met, the level is not evaluated and A31443 cannot be raised.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A31xxx group · SINAMICS manuals · Siemens manuals