SiemensETIJohnson ControlsIFMSICKWIKABosch RexrothELKO EPHYUNDAIABBVEGAKSR KUEBLERAlfa Laval

Alarm · SINAMICS G130, G150, S120, S150

A31429Encoder 1: Position difference hall sensor/track C/D and A/B too large

What it means

The drive monitors encoder 1 and raises this alarm when the measured position difference is too large: the error for track C/D is greater than +/-15 ° mechanical or +/-60 ° electrical, or the error for the Hall signals is greater than +/-60 ° electrical. For orientation: one period of track C/D corresponds to 360 ° mechanical, and one period of the Hall signal corresponds to 360 ° electrical. The monitoring responds, for example, when Hall sensors are connected as an equivalent for the C/D tracks with the incorrect rotational sense, or when the supply values are not accurate enough. Depending on the drive's configuration, the same condition can also be output as a fault or without any reaction.

Why it appears

  • The error for track C/D is greater than +/-15 ° mechanical or +/-60 ° electrical, or the error for the Hall signals is greater than +/-60 ° electrical.
  • Hall sensors are connected as an equivalent for the C/D tracks with the incorrect rotational sense.
  • The supply values are not accurate enough.
  • Track C or D is not connected.

What to check

  1. Read the alarm value in r2124 (interpret decimal): it shows the measured deviation as a mechanical angle if track C/D is affected, or as an electrical angle if the Hall signals are affected.
  2. Check whether track C or D is not connected.
  3. If Hall sensors are connected as an equivalent for track C/D, correct their direction of rotation.
  4. Check that the encoder cables are routed in compliance with EMC.
  5. Check the adjustment of the Hall sensor.

Reading the message value

  • The drive stores the measured deviation in r2124; interpret the value as a decimal number (16 bits with sign).
  • For track C/D: the measured deviation as a mechanical angle — 182 dec corresponds to 1 °.
  • For the Hall signals: the measured deviation as an electrical angle — 182 dec corresponds to 1 °.

Parameters the manual names

  • r2124 — the alarm value of this message: read it as a decimal to see the measured deviation (182 dec corresponds to 1 °) and whether track C/D or the Hall signals deviate.
  • p0491 — Motor encoder fault response ENCODER: the manual references it for this message; it governs how the drive responds when the condition is output as a fault, so check its setting if that happens.

Acknowledging and restarting

As an alarm, this message requires no acknowledgment from you and the drive takes no automatic action in response. If the drive's configuration outputs the same condition as a fault instead, it must be acknowledged immediately, and the drive's response then follows the encoder fault response set in p0491.

The same on every family

Every manual that describes A31429 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEActual position/speed value incorrect or not available (11)Encoder 1SINAMICS S120, S150 List Manual · p. 3054
G130, G150NONENONEActual position/speed value incorrect or not available (11)Encoder 1SINAMICS G130, G150 List Manual · p. 1739

The drives this code lives on

A31429 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A31429 mean on a SINAMICS drive?

The monitoring of encoder 1 has measured a position difference that is too large: above +/-15 ° mechanical (+/-60 ° electrical) for track C/D, or above +/-60 ° electrical for the Hall signals.

How do I fix alarm A31429?

Check whether track C or D is not connected, correct the direction of rotation of a Hall sensor connected as an equivalent for track C/D, route the encoder cables in compliance with EMC, and check the adjustment of the Hall sensor.

Where can I see how large the deviation is?

In r2124, interpreted as a decimal: a signed 16-bit value in which 182 dec corresponds to 1 ° — as a mechanical angle for track C/D and as an electrical angle for the Hall signals.

Does A31429 stop the drive, and does it need to be acknowledged?

As an alarm it triggers no automatic reaction and needs no acknowledgment. If the drive's configuration outputs the same condition as a fault instead, acknowledge it immediately; the response then follows p0491.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A31xxx group · SINAMICS manuals · Siemens manuals