What it means
A31419 appears when the drive must correct track A or B of Encoder 1 so strongly that the applied amplitude, phase or offset correction reaches its limit. The drive can output the same condition not only as alarm A31419 but also as fault F31419 or without an automatic reaction (N); the drive's configuration decides which variant applies. Neighbouring Encoder 1 messages (A31410, A31411, A31412, A31414, A31418, A31421, A31422, A31429) are described on their own pages.
Why it appears
- The amplitude/phase/offset correction for track A or B is at its limit — the correction has reached its minimum or maximum value.
- Amplitude error correction: the limit is reached when Amplitude B / Amplitude A = 0.78 ... 1.27.
- Phase error correction: the limit is reached when the phase is below 84 degrees or above 96 degrees.
- Offset correction: the limit is +/-140 mV for SMC20 and +/-650 mV for SMC10.
What to check
- Check the mechanical mounting tolerances for encoders without their own bearings (e.g. toothed-wheel encoders).
- Check the plug connections — including the transition resistance.
- Check the encoder signals.
- Replace the encoder or the encoder cable.
Reading the message value
The message value is the alarm value stored in r2124; interpret it hexadecimal. Each digit position of the value shows which correction has reached which limit:
- xxxx1: Minimum of the offset correction, track B
- xxxx2: Maximum of the offset correction, track B
- xxx1x: Minimum of the offset correction, track A
- xxx2x: Maximum of the offset correction, track A
- xx1xx: Minimum of the amplitude correction, track B/A
- xx2xx: Maximum of the amplitude correction, track B/A
- x1xxx: Minimum of the phase error correction
- x2xxx: Maximum of the phase error correction
- 1xxxx: Minimum of the cubic correction
- 2xxxx: Maximum of the cubic correction
Parameters the manual names
- r2124 (Alarm value): read the alarm value of this message here — interpreted hexadecimal, its digit positions identify which correction (offset, amplitude, phase or cubic) and which track has reached its limit.
- p0491 (Motor encoder fault response ENCODER): sets the fault response for the motor encoder, i.e. what the drive does if this condition is output as fault F31419.
Acknowledging and restarting
As alarm A31419 the drive takes no automatic action and the message requires no acknowledgement; eliminating the cause (see the checks above) is all that is needed. The same applies to the variant output without automatic reaction. If the condition is raised as fault F31419 instead, the drive executes the response configured for the drive object (ranging from NONE via OFF1, OFF2, OFF3 and STOP2 to ENCODER and IASC/DCBRK) and the fault can be acknowledged IMMEDIATELY; once the cause has been eliminated and the fault acknowledged, the drive can be restarted.
The same on every family
Every manual that describes A31419 gives it the same reaction, acknowledgement and message class.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS S120, S150 List Manual · p. 3052 |
| G130, G150 | NONE | NONE | Actual position/speed value incorrect or not available (11) | Encoder 1 | SINAMICS G130, G150 List Manual · p. 1738 |
The drives this code lives on
A31419 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A31419 mean?
The amplitude, phase or offset correction that the drive applies to Encoder 1 track A or B has reached its limit. The alarm value in r2124 shows which correction and which track are affected.
How do I clear A31419?
Check the mechanical mounting tolerances of encoders without their own bearings (e.g. toothed-wheel encoders), then the plug connections including transition resistance, then the encoder signals, and finally replace the encoder or encoder cable. As an alarm the message needs no acknowledgement.
What is the alarm value of A31419?
The drive stores it in r2124, interpreted hexadecimal. Each digit position identifies whether the minimum or maximum of the offset, amplitude, phase or cubic correction has been reached, and for which track.
Does A31419 stop the drive?
No — as an alarm the drive takes no automatic action and no acknowledgement is required. If the condition is output as fault F31419, the configured response applies and the fault is acknowledged IMMEDIATELY.