What it means
The drive raises A08760 when more process data have been mapped in a CAN PDO than the maximum size of the IF PZD (IF = interface) allows. The alarm signals a configuration problem: it triggers no drive reaction and stays in the alarm buffer until it is deleted. The alarm value the drive stores in r2124 tells you in which direction the limit was hit.
Why it appears
- The maximum size of the IF PZD was exceeded — too many process data are mapped in the PDO.
What to check
- Map fewer process data in the PDO so the maximum size of the IF PZD is no longer exceeded.
- Then delete the alarm with one of the following options: POWER ON (switch-off/switch-on), a warm restart (p0009 = 30, p0976 = 2), the CANopen NMT command reset node, a change of the CANopen NMT state, or deleting the alarm buffer [0...7] with p2111 = 0.
Reading the message value
The drive stores the alarm value in r2124; the manual says to interpret it as a decimal number:
- 1: error for IF PZD receive
- 2: error for IF PZD send
Parameters the manual names
- r2124 — read the stored alarm value as a decimal number to see whether the IF PZD error occurred on the receive side (1) or the send side (2).
- p0009 — set to 30 as part of the warm restart that deletes this alarm.
- p0976 — set to 2, together with p0009 = 30, to carry out that warm restart.
- p2111 — set to 0 to delete the alarms in alarm buffer [0...7] and clear A08760.
Acknowledging and restarting
No acknowledgement is required. Once the PDO mapping has been reduced, the alarm is removed by a POWER ON (switch-off/switch-on), a warm restart (p0009 = 30, p0976 = 2), the CANopen NMT command reset node, a change of the CANopen NMT state, or by setting p2111 = 0 to delete alarm buffer [0...7]. The manuals for all families describe the same procedure for this code.
What differs between the drive families
Straight from the manuals' own fields — A08760 is not described identically everywhere.
| Drive family | Reaction | Acknowledge | Message class | Component | Manual |
|---|---|---|---|---|---|
| S120, S150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS S120, S150 List Manual · p. 2930 |
| G130, G150 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | None | SINAMICS G130, G150 List Manual · p. 1644 |
| G120 | NONE | NONE | Error in the parameterization / configuration / commissioning procedure (18) | — | SINAMICS G120 · p. 902 |
The drives this code lives on
A08760 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.
Questions technicians ask
What does SINAMICS alarm A08760 mean?
More process data have been mapped in a CAN PDO than the maximum size of the IF PZD allows. The value in r2124 shows whether the error hit the receive path (1) or the send path (2).
How do I clear alarm A08760?
Map fewer process data in the PDO, then delete the alarm via POWER ON, a warm restart (p0009 = 30, p0976 = 2), a CANopen NMT reset node command, a change of the NMT state, or by setting p2111 = 0.
Does A08760 stop the drive or need an acknowledgement?
No. The alarm triggers no drive reaction and requires no acknowledgement; it simply remains in the alarm buffer until deleted with one of the options on this page.