Alarm · SINAMICS G120, G130, G150, S120, S150

A08759CAN: PDO COB-ID already available

What it means

A08759 is a CAN alarm with the title CAN: PDO COB-ID already available. It is raised when an already existing PDO COB-ID is allocated — in other words, a COB-ID that is already in use has been assigned again. The alarm points to the parameter in which this happened: the alarm value in r2124, read as a decimal number, is the parameter number. The manuals give a single remedy: select another PDO COB-ID.

Why it appears

  • An already existing PDO COB-ID was allocated, i.e. a COB-ID that is already in use was assigned again.

What to check

  1. Read the alarm value in r2124 as a decimal number — it contains the number of the parameter in which the already existing PDO COB-ID was allocated.
  2. The COB-ID concerned is included in index 0 of that parameter, so this is where the duplicate identifier sits.
  3. Select another PDO COB-ID, i.e. enter a COB-ID that is not already allocated.

Reading the message value

  • The alarm value is stored in r2124 and is interpreted as a decimal number; it contains the parameter number.
  • The message value is output as Parameter: %1; the placeholder stands for the number of the affected parameter.
  • The manual notes that the COB-ID is included in index 0.

Parameters the manual names

  • r2124 — alarm value: for this alarm it is interpreted as a decimal number and contains the number of the parameter in which the already existing PDO COB-ID was allocated.

Acknowledging and restarting

No acknowledgment is required for this alarm. The drive triggers no reaction to it and the message does not have to be acknowledged; selecting a PDO COB-ID that is not already in use is the whole remedy, and no reset step is needed beyond that.

What differs between the drive families

Straight from the manuals' own fields — A08759 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2930
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1644
G120NONENONEError in the parameterization / configuration / commissioning procedure (18)SINAMICS G120 · p. 902

The drives this code lives on

A08759 is described for G120, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A08759 mean on a SINAMICS drive?

It is a CAN alarm: an already existing PDO COB-ID was allocated, so an identifier that is already in use has been assigned again. The alarm value in r2124, read as a decimal number, names the parameter concerned.

How do I fix alarm A08759?

Select another PDO COB-ID — that is the remedy the manuals give. The alarm needs no acknowledgment, so there is nothing to reset once the duplicate allocation has been replaced.

Where do I find the COB-ID that triggered A08759?

The alarm value in r2124, interpreted as a decimal number, is the number of the affected parameter, and the manual notes that the COB-ID is included in index 0.

Does A08759 stop the drive?

No. No reaction is assigned to this alarm and it does not have to be acknowledged; it reports a configuration error that should still be corrected by selecting another PDO COB-ID.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A08xxx group · SINAMICS manuals · Siemens manuals