Alarm · SINAMICS G130, G150, S120, S150

A07941Sync-line-drive: Target frequency not permissible

What it means

The manuals print this alarm as Sync-line-drive: Target frequency not permissible. It belongs to the line-drive synchronization function and reports that the target frequency for the synchronization lies outside the permissible value range: it is either greater than the effective positive speed limit (r1084) or less than the effective negative speed limit (r1087). The alarm triggers no reaction and requires no acknowledgment; the condition no longer applies once the target frequency fulfills the conditions for line-drive synchronization.

Why it appears

  • The target frequency is outside the permissible value range: it is greater than the positive speed limit f_max (r1084) or less than the negative speed limit f_min (r1087).

What to check

  1. Read the alarm value in r2124 as a decimal number: 1084 means the target frequency is above the positive speed limit, 1087 means it is below the negative speed limit.
  2. Look at the effective limits that apply to the drive: r1084 (positive) and r1087 (negative).
  3. Compare the target frequency used for the line-drive synchronization with the limit named by the alarm value.
  4. Correct the target frequency so that it is neither greater than the positive limit (r1084) nor less than the negative limit (r1087) — so that it fulfills the conditions for the target frequency for line-drive synchronization.

Reading the message value

  • The alarm value is held in r2124 and must be interpreted as a decimal number.
  • The message value of the alarm refers to a parameter (the manual shows Parameter: %1).
  • 1084: Target frequency greater than the positive speed limit, f_sync > f_max (r1084).
  • 1087: Target frequency less than the negative speed limit, f_sync < f_min (r1087).

Parameters the manual names

  • r2124 (alarm value): holds the number that identifies which condition raised the alarm; read it as a decimal — 1084 or 1087.
  • r1084 (CO: Speed limit positive effective, n_limit pos eff): the effective positive speed limit; a target frequency above it gives the alarm value 1084.
  • r1087 (CO: Speed limit negative effective, n_limit neg eff): the effective negative speed limit; a target frequency below it gives the alarm value 1087.

Acknowledging and restarting

Nothing has to be acknowledged for this alarm. The target frequency for line-drive synchronization must fulfill the permissible conditions: not greater than the positive speed limit (r1084) and not less than the negative speed limit (r1087).

What differs between the drive families

Straight from the manuals' own fields — A07941 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEApplication/technological function faulted (17)NoneSINAMICS G130, G150 List Manual · p. 1616
S120, S150Application/technological function faulted (17)NoneSINAMICS S120, S150 List Manual · p. 2888

The drives this code lives on

A07941 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does alarm A07941 mean on a SINAMICS drive?

It reports that the target frequency for line-drive synchronization lies outside the permissible value range — above the effective positive speed limit (r1084) or below the effective negative speed limit (r1087).

How do I clear alarm A07941?

Read the alarm value in r2124 as a decimal number to see which limit is violated (1084 or 1087), then correct the target frequency so that it fulfills the conditions for line-drive synchronization. No acknowledgment is required.

Where is the alarm value of A07941 stored?

In r2124, interpreted as a decimal number: 1084 means the target frequency exceeds the positive limit f_max (r1084), 1087 means it is below the negative limit f_min (r1087).

Does alarm A07941 trip the drive?

No — the alarm triggers no reaction and needs no acknowledgment; it only reports that the target frequency is outside the effective speed limits.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.