Alarm · SINAMICS G130, G150, S120, S150

A01324Topology: Dummy drive object number incorrectly created

What it means

A01324 (Topology: Dummy drive object number incorrectly created) is raised when the list of the drive objects p0978 contains a dummy drive object number (255) at a position where the topology configuration does not allow it: in p0978, dummy drive object numbers are only permitted in the first partial list. The alarm value pinpoints the entry — r2124, interpreted as a decimal number, contains the index of p0978 under which the illegal value is located.

Why it appears

  • In p0978, a dummy drive object number (255) has been entered at an index that does not belong to the first partial list — dummy drive object numbers are only permitted in the first partial list of p0978.

What to check

  1. Set p0009 to 1 and then change p0978 so that the list satisfies all of the rules below.
  2. p0978 must include all of the drive object numbers (p0101).
  3. No drive object number may be entered twice.
  4. By entering a 0, the drive objects with PZD are separated from those without PZD.
  5. Only 2 partial lists are permitted; after the second 0, all values must be 0.
  6. Place every dummy drive object number (255) in the first partial list — nowhere else.

Reading the message value

  • Alarm value (r2124, interpret decimal): index of p0978 under which the illegal value is located.
  • Read r2124 as a decimal number to find the position in p0978 that must be corrected.

Parameters the manual names

  • p0978 — list of the drive objects: this is the list to correct, so that the dummy number 255 stands only in the first partial list.
  • p0009 — device commissioning parameter filter: set it to 1 so that p0978 can be changed.
  • p0101 — drive object numbers: p0978 must include every number from this list, without repetition.
  • r2124 — alarm value: read it as a decimal to get the index of p0978 where the illegal entry sits.

Acknowledging and restarting

This alarm only signals a faulty configuration and does not trip the drive, and it does not have to be acknowledged: once p0978 has been corrected to satisfy the rules above, the alarm is withdrawn.

The same on every family

Every manual that describes A01324 gives it the same reaction, acknowledgement and message class.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS G130, G150 List Manual · p. 1402
S120, S150NONENONEError in the parameterization / configuration / commissioning procedure (18)NoneSINAMICS S120, S150 List Manual · p. 2591

The drives this code lives on

A01324 is described for G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A01324 mean?

The topology configuration contains a dummy drive object number (255) in the list of drive objects p0978 at an index outside the first partial list, although dummy numbers are only permitted there.

How do I find the faulty entry for A01324?

The alarm value in r2124, interpreted as a decimal number, gives the index of p0978 under which the illegal value is located.

How is A01324 cleared?

Set p0009 to 1 and correct p0978: include all drive object numbers from p0101 without repetitions, use 0 to separate the PZD from the non-PZD drive objects, permit only 2 partial lists with all values 0 after the second 0, and keep the dummy numbers 255 in the first partial list. No acknowledgement is needed; the alarm clears once the list is right.