Alarm · SINAMICS G120, G120XA, G130, G150, S120, S150

A01251CU: CU-EEPROM incorrect read-write data

What it means

A01251 is raised by the Control Unit (CU) when it registers an error while reading the read-write data of its EEPROM (CU-EEPROM). The alarm concerns all drive objects. It travels with an alarm value held in r2124, which is read as a decimal number; the manual decodes no individual values and states that this value is Only for internal Siemens troubleshooting. Which remedy applies depends on whether the value in r2124 is below 256 or 256 and above.

Why it appears

  • The Control Unit has detected an error while reading the read-write data of its EEPROM; this is the only cause the manuals give for this alarm.

What to check

  1. Read the alarm value in r2124 and interpret it as a decimal number — the manuals note that this value serves only for internal Siemens troubleshooting.
  2. Value below 256: carry out a POWER ON (switch the power off and on again). If the alarm still comes back, replace the Control Unit.
  3. Value 256 or above: clear the fault memory of the drive object that raised this alarm (p0952 = 0). Alternatively, clear the fault memory of all drive objects in one step (p2147 = 1); this alternative is printed for G130, G150, S120 and S150. If the alarm still comes back, replace the Control Unit.

Reading the message value

  • The drive stores the alarm value belonging to this alarm in r2124; interpret the value as a decimal number.
  • No decoding of individual values is printed — the value is stated to serve only for internal Siemens troubleshooting.

Parameters the manual names

  • r2124 — alarm value: read it as a decimal number to decide between the two remedy branches (below 256, or 256 and above).
  • p0952 — set to 0 to clear the fault memory of the drive object that raised this alarm; applies when the value in r2124 is 256 or above.
  • p2147 — set to 1 to clear the fault buffer of all drive objects at once, as the alternative to p0952; given in the manuals for G130, G150, S120 and S150.

Acknowledging and restarting

This alarm needs no separate acknowledgement: it is cleared by the remedy itself — a POWER ON when the value in r2124 is below 256, or clearing the fault memory when it is 256 or above. If the alarm keeps returning after that, the Control Unit must be replaced.

What differs between the drive families

Straight from the manuals' own fields — A01251 is not described identically everywhere.

Drive familyReactionAcknowledgeMessage classComponentManual
G130, G150NONENONEHardware/software error (1)Control Unit (CU)SINAMICS G130, G150 List Manual · p. 1396
S120, S150Hardware/software error (1)Control Unit (CU)SINAMICS S120, S150 List Manual · p. 2584
G120NONENONEHardware/software error (1)SINAMICS G120 · p. 832
G120XANONENONESINAMICS G120XA PN converter · p. 1109

The drives this code lives on

A01251 is described for G120, G120XA, G130, G150, S120, S150. These are the converters of those families in our catalogue — price on request.

Questions technicians ask

What does SINAMICS alarm A01251 mean?

The Control Unit has registered an error when reading the read-write data of its EEPROM. The alarm value in r2124 is, per the manual, meant only for internal Siemens troubleshooting.

How do I clear alarm A01251?

Read r2124 as a decimal number: below 256, carry out a POWER ON; at 256 or above, clear the fault memory with p0952 = 0 (or p2147 = 1 for all drive objects). If the alarm persists, replace the Control Unit.

What is r2124 for alarm A01251?

It holds the alarm value, which you interpret as a decimal number. The manual gives no decoding — it states the value serves only for internal Siemens troubleshooting, and it decides which remedy branch applies.

Codes next to this one

Source

Written from Siemens' own List Manuals and operating instructions; every number, designation and parameter on this page is checked against them before publication.

All SINAMICS codes: fault and alarm codes · the A01xxx group · SINAMICS manuals · Siemens manuals